Specifications

Identification

3VA2340-6JP32-0DL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2340-6JP32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22

Ratings

3VA2340-6JP32-0DL0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C375 A
Current at 60 °C350 A
Current at 65 °C325 A
Current at 70 °C300 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.98.5 W

Protection & Trip Unit

3VA2340-6JP32-0DL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2340-6JP32-0DL0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2340-6JP32-0DL0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4

Environmental

3VA2340-6JP32-0DL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2340-6JP32-0DL0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

Product Identity and Key Ratings

The 3VA2340-6JP32-0DL0: Breaking capacity varies with voltage: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 7.5 kA at 690 V. These figures define the fault-current interruption capability at each voltage level — critical for coordination studies. Thermal derating applies above 50 °C: the breaker holds 400 A up to 50 °C, then drops to 375 A at 55 °C, 350 A at 60 °C, 325 A at 65 °C, and 300 A at 70 °C. Ambient temperature in the enclosure must be factored into the continuous load calculation.

Auxiliary and Communication Features

This variant includes a communication function, an undervoltage release (UVR), and a complement of auxiliary switches: 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch (HQ design). The trip indicator is present, and there is no voltage trigger or ground-fault monitoring.

Dimensions and Mounting

Dimensions are 248 mm height, 138 mm width, and 110 mm depth (9.76 × 5.43 × 4.33 in). The MCCB mounts on a DIN rail or panel — typical for SENTRON switchgear assemblies.

Frequently asked questions

Where can I buy 3VA2340-6JP32-0DL0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA2340-6JP32-0DL0 at 240 V?

The breaking capacity is 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 7.5 kA at 690 V.

Does 3VA2340-6JP32-0DL0 include communication and auxiliary switches?

Yes, it includes a communication function, an undervoltage release, 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch.

MPN