Siemens 3VA2340-6JP32-0JA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2340-6JP32-0JA0 SENTRON MCCB, 400 A, 3-Pole, Line

MPN3VA2340-6JP32-0JA0

Siemens SENTRON 3VA2340-6JP32-0JA0, molded case circuit breaker, 3-pole, 400 A rated continuous current, line protection, ETU550 electronic trip unit, breaking capacity 242 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2340-6JP32-0JA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2340-6JP32-0AA0

Ratings

3VA2340-6JP32-0JA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C375 A
Current at 60 °C350 A
Current at 65 °C325 A
Current at 70 °C300 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V40 kA
Power loss, max.96 W

Protection & Trip Unit

3VA2340-6JP32-0JA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550

Construction & Connection

3VA2340-6JP32-0JA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2340-6JP32-0JA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2340-6JP32-0JA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2340-6JP32-0JA0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

400 A MCCB with ETU550 — line protection for main feeders

The Siemens SENTRON 3VA2340-6JP32-0JA0 is a 3-pole molded case circuit breaker rated for 400 A continuous current, configured for line protection with an ETU550 electronic trip unit. It carries a breaking capacity of 242 kA at 240 V, stepping down through 187 kA at 415 V and 440 V, 121 kA at 500 V, and 40 kA at 690 V — so it handles high-fault main feeders where the upstream transformer can deliver serious short-circuit energy. The thermal derating curve holds full 400 A up to 50 °C, then drops to 375 A at 55 °C, 350 A at 60 °C, 325 A at 65 °C, and 300 A at 70 °C; if your panel ambient runs hot, size the breaker for the actual enclosure temperature, not the nameplate.

What the ratings mean for your panel

The 400 A rated continuous current (Iu) is the breaker's thermal capacity under normal load — it's the number you match to your feeder ampacity. The ETU550 electronic trip unit gives you adjustable long-time, short-time, instantaneous, and ground-fault protection curves, which means you can coordinate selectivity downstream without nuisance trips. The breaking capacities at each voltage level tell you the maximum fault current the breaker can safely interrupt at that voltage; at 690 V it's still 40 kA, so it works on 480 V or 600 V class systems with headroom. The 800 V rated insulation voltage (Ui) confirms the internal clearance is rated for 690 V nominal systems.

Mounting and panel fit

Dimensions are 248 mm height, 138 mm width, 110 mm depth — a standard SENTRON 3VA2 frame size. It mounts on a DIN rail or can be screw-fixed to a backplate; the 110 mm depth includes the arc chamber and terminals, so allow clearance for cable bending radius below the breaker. The 3-pole block fits a 138 mm wide slot in a distribution panel or motor control center bucket.

Trip unit and auxiliary functions

The ETU550 trip unit includes a voltage trigger function and communication capability, so it can report status or accept a remote trip signal on a digital network. No auxiliary contact is fitted as standard, and there is no undervoltage release or ground-fault monitoring module on this variant — those would need to be ordered as separate accessories if your application requires them. The mechanical endurance is rated at 15,000 operations, which is typical for a main breaker that sees infrequent switching.

Environmental limits

Operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C. Maximum power loss at rated current is 96 W — that's the heat the breaker dissipates into the enclosure, so factor it into your panel cooling calculation, especially if multiple breakers are ganged in a small cabinet.

Frequently asked questions

Where can I buy 3VA2340-6JP32-0JA0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the breaking capacity of 3VA2340-6JP32-0JA0 at different voltages?

242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 40 kA at 690 V — sufficient for main feeders with high fault current potential.

Does 3VA2340-6JP32-0JA0 include a shunt trip or auxiliary contacts?

It includes a shunt trip (STL) release as the auxiliary release design, but no auxiliary contact block is fitted as standard. The shunt trip order code is 3VA9688-0BL32.

What compliance documentation is available for 3VA2340-6JP32-0JA0?

As a Siemens SENTRON MCCB, it carries applicable IEC and UL certifications for the class. Specific RoHS, REACH, and UL documentation is available from the manufacturer upon request.

MPN
3VA2340-6JP32-0JA0