Skip to main content
Siemens 3VA2340-6JP32-0KC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2340-6JP32-0KC0 SENTRON MCCB, 400 A, 242 kA IC

MPN3VA2340-6JP32-0KC0

Siemens SENTRON 3VA2340-6JP32-0KC0, molded case circuit breaker, 3-pole, 400 A, 242 kA at 240 V AC, line protection, ETU550 electronic trip unit, current production.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2340-6JP32-0KC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2340-6JP32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA2340-6JP32-0KC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C375 A
Current at 60 °C350 A
Current at 65 °C325 A
Current at 70 °C300 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V40 kA
Power loss, max.96 W
3VA2340-6JP32-0KC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
3VA2340-6JP32-0KC0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2340-6JP32-0KC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2340-6JP32-0KC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2340-6JP32-0KC0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

The Siemens 3VA2340-6JP32-0KC0 is a SENTRON molded case circuit breaker (MCCB) rated for 400 A continuous at 40 °C, with a 242 kA interrupting capacity at 240 V AC. It's a line-protection variant with an ETU550 electronic trip unit and built-in communication capability — meaning you can pull current and status data upstream without adding a separate metering module. This is a current-production part, so no last-time-buy scramble.

The 400 A rating holds at 40 °C ambient, but above that you lose headroom: 375 A at 55 °C, 350 A at 60 °C, 325 A at 65 °C, and 300 A at 70 °C. If your enclosure runs warm — say a packed MCC lineup — size the breaker for the actual ambient, not the nameplate. The ETU550 trip unit gives you LSIG (long-time, short-time, instantaneous, ground-fault) adjustability, so coordination studies are practical. Breaking capacity scales with system voltage: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 40 kA at 690 V. At 415 V — common in industrial distribution — 187 kA is well above typical fault levels, giving selectivity headroom without cascading upstream.

Integration and auxiliary options

Three-pole, 138 mm wide, 248 mm tall, 110 mm deep. The depth is the dimension that catches people on retrofit — check that the existing enclosure has clearance for the rear arc-chamber exhaust. The basic switch (the breaker body without electronics) is order code 3VA2340-6JP32-0AA0, and the integrated auxiliary trip module is 3VA9688-0BL33 — useful if you're ordering spares or building a replacement from sub-assemblies.

Frequently asked questions

Where can I buy 3VA2340-6JP32-0KC0 and how do I get a price?

Sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time.

What is the breaking capacity of this MCCB at different voltages?

242 kA at 240 V AC, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 40 kA at 690 V.

What trip unit does this breaker use?

It uses the ETU550 electronic trip unit with LSIG protection (long-time, short-time, instantaneous, ground-fault).

Does this MCCB have communication capability?

Yes, it has a communication function built in, allowing current and status data to be read remotely.

MPN
3VA2340-6JP32-0KC0