Skip to main content
Siemens 3VA2340-6JQ32-0CC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2340-6JQ32-0CC0 SENTRON MCCB, 400 A, 242 kA at 24

MPN3VA2340-6JQ32-0CC0

Siemens SENTRON 3VA2340-6JQ32-0CC0, molded case circuit breaker, 3-pole, 400 A, 242 kA at 240 V, line protection, undervoltage release, communication function.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2340-6JQ32-0CC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2340-6JQ32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA2340-6JQ32-0CC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C375 A
Current at 60 °C350 A
Current at 65 °C325 A
Current at 70 °C300 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.98.5 W
3VA2340-6JQ32-0CC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560
Overcurrent protection functionLSIG
Ground-fault monitoringSummation current formation L-conductor
Grounding protection functionYes
3VA2340-6JQ32-0CC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2340-6JQ32-0CC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2340-6JQ32-0CC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2340-6JQ32-0CC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

The Siemens SENTRON 3VA2340-6JQ32-0CC0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying a full-scale current of 400 A and an adjustable thermal-magnetic trip range from 600 A minimum to 4000 A maximum. Its interrupting capacity hits 242 kA at 240 V AC and 187 kA at 415/440 V, dropping to 121 kA at 500 V and 7.5 kA at 690 V — so for most 400 V class distribution panels this breaker clears faults well into the high-fault zone without cascading upstream.

Thermal derating and ambient compensation

Above that it derates linearly: 375 A at 55 °C, 350 A at 60 °C, 325 A at 65 °C, and 300 A at 70 °C.

Auxiliaries and communication

This variant ships with two HQ auxiliary switches and an undervoltage release (UVR) fitted. Communication function is onboard, so it can report status or accept remote commands over the SENTRON bus system.

Listed as current production.

Physical fit

Frequently asked questions

Does 3VA2340-6JQ32-0CC0 include an undervoltage release?

Yes, it ships with an undervoltage release (UVR) and two HQ auxiliary switches.

MPN
3VA2340-6JQ32-0CC0