Skip to main content
Siemens 3VA2340-6JQ32-0DC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2340-6JQ32-0DC0 SENTRON MCCB, 400 A, 242 kA at 24

MPN3VA2340-6JQ32-0DC0

Siemens SENTRON 3VA2340-6JQ32-0DC0, molded case circuit breaker, 3-pole, 400 A, interrupting 242 kA at 240 V, 187 kA at 415 V, line protection, with undervoltage release and communication function.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2340-6JQ32-0DC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2340-6JQ32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2340-6JQ32-0DC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C375 A
Current at 60 °C350 A
Current at 65 °C325 A
Current at 70 °C300 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.98.5 W

Protection & Trip Unit

3VA2340-6JQ32-0DC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560
Overcurrent protection functionLSIG
Ground-fault monitoringSummation current formation L-conductor
Grounding protection functionYes

Construction & Connection

3VA2340-6JQ32-0DC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2340-6JQ32-0DC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2340-6JQ32-0DC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2340-6JQ32-0DC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

What this MCCB delivers on the line

The Siemens SENTRON 3VA2340-6JQ32-0DC0 is a 3-pole molded case circuit breaker rated for line protection at 400 A continuous (full-scale value 400 A, initial value 80 A). Its interrupting capacity reaches 242 kA at 240 V, 187 kA at 415 V and at 440 V, 121 kA at 500 V, and 7.5 kA at 690 V — so at the common 415 V distribution level it clears a 187 kA fault without upstream cascading. The breaker includes an undervoltage release (UVR) and a communication function, plus two auxiliary switches (HQ design).

Thermal derating and panel fit

The breaker carries its full 400 A rating from 40 °C through 50 °C ambient. Above that it derates: 375 A at 55 °C, 350 A at 60 °C, 325 A at 65 °C, and 300 A at 70 °C. Operating temperature range is -25 °C to +70 °C; storage range is -40 °C to +80 °C. Maximum power loss is 98.5 W. Mounting dimensions: 248 mm height, 138 mm width, 110 mm depth — fits standard panel cutouts for this frame class.

Frequently asked questions

Who supplies 3VA2340-6JQ32-0DC0 and how is it quoted for volume purchases?

This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is 3VA2340-6JQ32-0DC0's interrupting capacity at 415 V?

At 415 V the interrupting capacity is 187 kA.

What compliance documentation does this brand provide for 3VA2340-6JQ32-0DC0?

The evidence does not list specific compliance documents (RoHS, REACH, UL, IEC) for this order code. Standard SENTRON MCCB documentation applies; verify with the manufacturer for your jurisdiction.

MPN
3VA2340-6JQ32-0DC0