Skip to main content
Siemens 3VA2340-6JQ32-0DL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2340-6JQ32-0DL0 SENTRON MCCB, 400 A, 242 kA

MPN3VA2340-6JQ32-0DL0

Siemens SENTRON 3VA2340-6JQ32-0DL0, molded case circuit breaker, 3-pole, 400 A, line protection, ETU560 electronic trip unit, 242 kA at 240 V, undervoltage release, communication capable.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2340-6JQ32-0DL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2340-6JQ32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22

Ratings

3VA2340-6JQ32-0DL0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C375 A
Current at 60 °C350 A
Current at 65 °C325 A
Current at 70 °C300 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V40 kA
Power loss, max.98.5 W

Protection & Trip Unit

3VA2340-6JQ32-0DL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560

Construction & Connection

3VA2340-6JQ32-0DL0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2340-6JQ32-0DL0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4

Environmental

3VA2340-6JQ32-0DL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2340-6JQ32-0DL0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

400 A MCCB with ETU560 — what the ratings mean for your panel

The Siemens SENTRON 3VA2340-6JQ32-0DL0 is a 3-pole molded case circuit breaker rated for 400 A continuous current (Iu) across the 40 °C to 50 °C ambient band — no derating needed in that range. Above 50 °C the curve steps down: 375 A at 55 °C, 350 A at 60 °C, 325 A at 65 °C, and 300 A at 70 °C. That means a panel running at 40 °C ambient gets the full 400 A; if the enclosure runs hot, you lose 25 A per 5 °C rise above 50 °C. Breaking capacity is 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 40 kA at 690 V. For a 480 V distribution panel (common in North America), the 187 kA at 440 V figure is the closest published value — well above typical available fault current in most industrial switchboards. The ETU560 electronic trip unit handles the protection curve. An undervoltage release (UVR) is built in, and the auxiliary contact set includes two auxiliary switches, one trip alarm switch, and one electrical alarm switch. Communication function is present, so the breaker can report status to a higher-level control system.

Integration and mounting dimensions

The breaker measures 248 mm high, 138 mm wide, and 110 mm deep. That 110 mm depth is the dimension that matters for enclosure depth clearance — check your gland plate or back-panel clearance before committing the cutout. The 138 mm width is the panel cutout width for a 3-pole frame; verify against your existing busbar or riser spacing.

Included releases and accessories

The base switch is order code 3VA2340-6JQ32-0AA0. The integrated auxiliary trip is 3VA9608-0BB25. The undervoltage release is designed for summation current formation on the L-conductor for ground fault monitoring. Power loss at rated current is 98.5 W maximum — factor that into your enclosure thermal budget.

Frequently asked questions

How do I get current pricing and availability for 3VA2340-6JQ32-0DL0?

Pricing and availability are confirmed at quote time against an RFQ. Submit a request through the storefront; the sourcing desk will return current lead time and per-unit pricing from the independent distribution network.

What is the breaking capacity of this MCCB at 240 V?

The rated breaking capacity is 242 kA at 240 V. At 415 V and 440 V it is 187 kA, at 500 V it is 121 kA, and at 690 V it is 40 kA.

What trip unit does 3VA2340-6JQ32-0DL0 use?

It uses the ETU560 electronic overcurrent release. The breaker also includes an undervoltage release (UVR) and a communication function for remote monitoring.

What are the physical dimensions of this breaker?

Height is 248 mm, width is 138 mm, and depth is 110 mm. The depth is the critical dimension for enclosure clearance.

MPN
3VA2340-6JQ32-0DL0