Skip to main content
Siemens 3VA2340-6JQ32-0JL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2340-6JQ32-0JL0 SENTRON MCCB, 400 A, 65 kA at 415

MPN3VA2340-6JQ32-0JL0

Siemens SENTRON 3VA2340-6JQ32-0JL0, molded case circuit breaker, 3-pole, line protection, 400 A, 65 kA at 415 V, with communication function.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2340-6JQ32-0JL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2340-6JQ32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22

Ratings

3VA2340-6JQ32-0JL0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C375 A
Current at 60 °C350 A
Current at 65 °C325 A
Current at 70 °C300 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.96 W

Protection & Trip Unit

3VA2340-6JQ32-0JL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560
Overcurrent protection functionLSIG
Ground-fault monitoringSummation current formation L-conductor
Grounding protection functionYes

Construction & Connection

3VA2340-6JQ32-0JL0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2340-6JQ32-0JL0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4

Environmental

3VA2340-6JQ32-0JL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2340-6JQ32-0JL0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

Line protection MCCB with communication — 400 A frame, 65 kA at 415 V

The Siemens 3VA2340-6JQ32-0JL0 is a SENTRON molded case circuit breaker (MCCB) designed for line protection in main distribution panels. It carries a 400 A continuous rating at 40 °C and an adjustable overcurrent trip range from 600 A to 4 000 A, giving the site engineer selectivity headroom downstream. The interrupting capacity hits 242 kA at 240 V and 187 kA at 415 V — enough to handle high-fault utility feeds without cascading upstream. Three-pole construction, 248 mm tall, 138 mm wide, 110 mm deep. The depth is the dimension that matters most in retrofit panels — at 110 mm it fits standard MCCB compartments without gland-plate interference.

Thermal derating and trip unit

Rated 400 A from 40 °C through 50 °C ambient. Above that, derate linearly: 375 A at 55 °C, 350 A at 60 °C, 325 A at 65 °C, 300 A at 70 °C. If the panel internal ambient runs hot — common in compact switchboards — the 55 °C derating to 375 A is the figure to budget against. Electronic trip unit with LSIG functions: long-time (L), short-time (S), instantaneous (I), and ground-fault (G). Initial setting at 80 A, full-scale 400 A. Trip indicator and voltage trigger are both present — useful for remote fault annunciation via the communication function.

Auxiliary switches and shunt trip

Factory-fitted with 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch (HQ configuration). Also includes a shunt trip (STL) for remote opening via a control signal. The auxiliary switch count is enough to report breaker position to a PLC, interlock a downstream contactor, and drive a panel lamp — all from one device. The supplied basic switch variant is 3VA2340-6JQ32-0AA0 — the base MCCB without the communication module. This -0JL0 suffix adds the communication function, so if the BOM calls for a breaker that talks to a building management system, this is the variant.

Frequently asked questions

What is the interrupting capacity of 3VA2340-6JQ32-0JL0 at 415 V?

187 kA at 415 V. At 240 V it is 242 kA, at 500 V it is 121 kA, and at 690 V it is 7.5 kA.

Where can I buy 3VA2340-6JQ32-0JL0?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
3VA2340-6JQ32-0JL0