The Siemens 3VA2340-6JQ42-0DJ0 is a 4-pole IEC frame 400 circuit breaker with a breaking capacity class H rating of 85 kA at 415 V — that is the maximum fault current it can safely interrupt without damage, sized for high-fault-capacity industrial distribution panels where upstream coordination demands a robust interrupting rating. The ETU560 electronic trip unit provides LSIG protection (long-time, short-time, instantaneous, and ground-fault) with an adjustable overload protection range Ir = 160 A to 400 A, short-circuit protection Isd = 0.6 to 10× In, and instantaneous pickup Ii = 1.5 to 10× In. Ground-fault protection is switchable with Ig adjustable from 0.2 to 1× In and time delay tg = 0.05 to 0.8 s. This level of adjustability lets the breaker be fine-tuned for cable protection, motor branch circuits, or transformer feeders without swapping trip units. Neutral conductor protection is adjustable (OFF, up to 100% of In), and the breaker includes a nut keeper kit, an undervoltage release rated 208–230 V AC 50/60 Hz, two auxiliary switches, and one trip alarm switch — all factory-integrated, so no separate accessory ordering for these functions.

Siemens 3VA2340-6JQ42-0DJ0 Circuit Breaker, 400A, 85kA @ 415
MPN3VA2340-6JQ42-0DJ0
Siemens 3VA2 IEC frame 400, breaking capacity class H, Icu=85kA @ 415V, 4-pole, line protection ETU560, LSIG, In=400A.
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026
Product details
Frequently asked questions
What is the breaking capacity of 3VA2340-6JQ42-0DJ0?
The breaker is rated Icu = 85 kA at 415 V, placing it in breaking capacity class H for the IEC frame 400 platform.
What trip unit does this breaker use?
It uses an ETU560 electronic trip unit with LSIG protection — long-time, short-time, instantaneous, and ground-fault — with adjustable settings for overload, short-circuit, and ground-fault parameters.
MPN
3VA2340-6JQ42-0DJ0