Skip to main content
Siemens 3VA2340-6KP32-0AD0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2340-6KP32-0AD0 SENTRON MCCB, 400 A, 3-Pole, Line

MPN3VA2340-6KP32-0AD0

Siemens SENTRON 3VA2340-6KP32-0AD0, molded case circuit breaker, 3-pole, 400 A, line protection, ETU850 electronic trip unit, 242 kA at 240 V, 187 kA at 415 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2340-6KP32-0AD0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2340-6KP32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA2340-6KP32-0AD0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C375 A
Current at 60 °C350 A
Current at 65 °C325 A
Current at 70 °C300 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V40 kA
Power loss, max.96 W
3VA2340-6KP32-0AD0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
3VA2340-6KP32-0AD0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2340-6KP32-0AD0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts3
3VA2340-6KP32-0AD0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2340-6KP32-0AD0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

The Siemens SENTRON 3VA2340-6KP32-0AD0 is a 3-pole molded case circuit breaker (MCCB) rated for 400 A continuous current at 40 °C, configured for line protection with an ETU850 electronic trip unit.

The 400 A rating holds flat from 40 °C to 50 °C, then derates linearly to 300 A at 70 °C. If your enclosure ambient runs above 50 °C, you lose 25 A per 5 °C step — plan the thermal budget accordingly.

Communication and auxiliary contacts

Account for handle throw and rear terminals when sizing enclosure depth.

Frequently asked questions

What is 3VA2340-6KP32-0AD0's listed depth?

The depth is 110 mm, excluding handle throw and rear terminal projections.

MPN
3VA2340-6KP32-0AD0