The breaker includes a communication function for integration into a plant monitoring system, and its 138 mm width and 248 mm height fit standard MCCB mounting footprints in switchboards.
Above that the thermal curve drops: 375 A at 55 °C, 350 A at 60 °C, 325 A at 65 °C, and 300 A at 70 °C. The maximum power loss is 96 W, so enclosure ventilation matters in a sealed cabinet.
Interrupting capacity across voltage levels
The interrupting ratings drop sharply as voltage rises: 242 kA at 240 V, 187 kA at both 415 V and 440 V, 121 kA at 500 V, and 7.5 kA at 690 V.
Auxiliary contacts and basic switch
The basic switch assembly is order code 3VA2340-6KP32-0AA0.