Skip to main content
Siemens 3VA2340-6KP32-0BA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2340-6KP32-0BA0 SENTRON MCCB, 400 A, 3-Pole

MPN3VA2340-6KP32-0BA0

Siemens SENTRON 3VA2340-6KP32-0BA0, molded case circuit breaker, 3-pole, 400 A continuous, 242 kA breaking capacity at 240 V, line protection design, with undervoltage release and communication function.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2340-6KP32-0BA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2340-6KP32-0AA0

Ratings

3VA2340-6KP32-0BA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C375 A
Current at 60 °C350 A
Current at 65 °C325 A
Current at 70 °C300 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.98.5 W

Protection & Trip Unit

3VA2340-6KP32-0BA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2340-6KP32-0BA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2340-6KP32-0BA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2340-6KP32-0BA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2340-6KP32-0BA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

What ships in the carton

The Siemens SENTRON 3VA2340-6KP32-0BA0 is a 3-pole molded case circuit breaker rated for 400 A continuous current at 40 °C, designed for line protection in distribution panels. Breaking capacity hits 242 kA at 240 V and 187 kA at 415 V, so it handles high-fault service-entrance or feeder duty without cascading upstream. The unit ships with an integrated undervoltage release (UVR) and onboard communication function — no auxiliary switch module to order separately. Kit is complete: the breaker, UVR, and comms interface are all in the carton.

Thermal derating — the real continuous current

The 400 A rating holds flat from 40 °C through 50 °C ambient. Above that, the frame derates linearly: 375 A at 55 °C, 350 A at 60 °C, 325 A at 65 °C, and 300 A at 70 °C. If the panel ambient runs hot — say, a packed enclosure near a furnace line — size the load at the derated figure, not the nameplate 400 A. The 70 °C ceiling matches the maximum operating temperature spec, so the breaker itself is fine; the load current is what drops.

Breaking capacity by voltage level

This MCCB delivers 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 7.5 kA at 690 V. The steep drop at 690 V means it is not a universal high-voltage breaker — use it on 240–500 V systems where the SCCR matches. For 690 V applications, the 7.5 kA figure limits it to low-fault installations or requires upstream current-limiting fuses.

Panel fit and dimensions

Dimensions are 248 mm high, 138 mm wide, 110 mm deep. The 3-pole frame mounts on a standard DIN rail or panel-mount base in a distribution board. The 110 mm depth leaves clearance for rear-connected busbars or cable lugs. Verify the enclosure depth against the 110 mm plus wire-bending space — standard 200 mm deep enclosures work, shallow troughs may not.

Frequently asked questions

Where can I buy 3VA2340-6KP32-0BA0 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock figures or lead-time numbers on this page.

What is the continuous current rating of 3VA2340-6KP32-0BA0?

400 A continuous at 40 °C ambient, holding flat through 50 °C, then derating to 300 A at 70 °C.

What breaking capacity does this MCCB provide at 240 V and 415 V?

242 kA at 240 V and 187 kA at 415 V, making it suitable for high-fault service-entrance or feeder applications at those voltage levels.

Does 3VA2340-6KP32-0BA0 include an undervoltage release?

Yes, it ships with an integrated undervoltage release (UVR) as the auxiliary release — no separate module to order.

MPN