Skip to main content
Siemens 3VA2340-7HL32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2340-7HL32-0AA0 MCCB, 400 A, ETU320

MPN3VA2340-7HL32-0AA0
Active

Siemens SENTRON 3VA2340-7HL32-0AA0 molded case circuit breaker, 3-pole, 400 A continuous, ETU320 electronic trip unit, line protection design, 330 kA interrupting at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2340-7HL32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2340-7HL32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C385 A
Current at 60 °C370 A
Current at 65 °C355 A
Current at 70 °C340 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.96 W
3VA2340-7HL32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2340-7HL32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2340-7HL32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2340-7HL32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2340-7HL32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

It carries the ETU320 electronic trip unit, which provides adjustable long-time and short-time delay curves plus instantaneous protection — a solid choice for feeder or main breaker duty where selectivity and coordination matter.

The 400 A continuous rating holds flat from 40 °C through 50 °C, then derates to 385 A at 55 °C, 370 A at 60 °C, 355 A at 65 °C, and 340 A at 70 °C. If your enclosure runs hot, you lose 15 % of capacity at the top of the ambient range — factor that into your load budget. Interrupting capacity is 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 7.5 kA at 690 V. Maximum power loss is 96 W at rated current. That heat stays inside the enclosure; make sure your thermal calculation accounts for it, especially in a multi-breaker lineup.

What the trip unit gives you

It supports long-time pickup and delay, short-time pickup and delay (with I²t on/off), and instantaneous pickup.

It mounts via the standard MCCB footprint — four-bolt pattern, rear or front terminals depending on the accessory kit. No DIN-rail clip; this is a bolted-frame breaker for fixed installation in a distribution board or switchgear cubicle.

MPN