Skip to main content
Siemens 3VA2340-7HL32-0BC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2340-7HL32-0BC0 SENTRON MCCB, 400 A, 3-Pole, 330

MPN3VA2340-7HL32-0BC0

Siemens SENTRON 3VA2340-7HL32-0BC0, molded case circuit breaker, 3-pole, 400 A continuous, 330 kA breaking capacity at 240 V, line protection design, with undervoltage release and 2 auxiliary switches HQ.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2340-7HL32-0BC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2340-7HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2340-7HL32-0BC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C385 A
Current at 60 °C370 A
Current at 65 °C355 A
Current at 70 °C340 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.98.5 W

Protection & Trip Unit

3VA2340-7HL32-0BC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2340-7HL32-0BC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2340-7HL32-0BC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2340-7HL32-0BC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2340-7HL32-0BC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

What this MCCB delivers on the line side

The Siemens 3VA2340-7HL32-0BC0 is a 3-pole SENTRON molded case circuit breaker rated for 400 A continuous current at 40 °C, with a maximum breaking capacity of 330 kA at 240 V. That 330 kA figure means it can safely interrupt a fault current up to that level without upstream cascading — critical for high-fault installations like utility-scale PV inverters or large motor control centers where the available fault current can exceed 200 kA. The breaker holds its full 400 A rating up to 50 °C; above that it derates linearly to 340 A at 70 °C, so panel ambient temperature must be factored into the continuous load. This is a line-protection design (not motor-protection), so it's intended for feeder or main breaker duty where the load is a distribution bus, not a single motor. It ships with an undervoltage release (UVR) and two HQ auxiliary switches, which means it's ready for remote trip indication and undervoltage protection without adding accessories. The supplied basic switch is order code 3VA2340-7HL32-0AA0.

Panel fit and integration

Dimensions are 248 mm high, 138 mm wide, 110 mm deep — a standard MCCB footprint that fits most DIN-rail or panel-mount enclosures. The 110 mm depth means it will clear a 120 mm deep enclosure without interference, but a 100 mm deep enclosure is too tight. Power loss at rated current is 98.5 W, so ventilation or derating may be needed in sealed cabinets.

Frequently asked questions

Who supplies 3VA2340-7HL32-0BC0 and how is it quoted for volume purchases?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA2340-7HL32-0BC0 at different voltages?

Breaking capacity is 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 7.5 kA at 690 V.

What accessories are included with 3VA2340-7HL32-0BC0?

It includes an undervoltage release (UVR) and two HQ auxiliary switches.

MPN
3VA2340-7HL32-0BC0