Skip to main content
Siemens 3VA2340-7HL32-0BL0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2340-7HL32-0BL0 MCCB, 400 A, 3-pole, 330

MPN3VA2340-7HL32-0BL0

Siemens SENTRON 3VA2340-7HL32-0BL0, molded case circuit breaker, 3-pole, 400 A continuous, line protection, with undervoltage release and auxiliary switches.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2340-7HL32-0BL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2340-7HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22
3VA2340-7HL32-0BL0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C385 A
Current at 60 °C370 A
Current at 65 °C355 A
Current at 70 °C340 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.98.5 W
3VA2340-7HL32-0BL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2340-7HL32-0BL0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2340-7HL32-0BL0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4
3VA2340-7HL32-0BL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2340-7HL32-0BL0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

Its interrupting capacity hits 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 7.5 kA at 690 V — so it handles high-fault utility feeds or transformer secondaries without cascading upstream. The continuous rating holds at 400 A through 50 °C, then derates to 385 A at 55 °C, 370 A at 60 °C, 355 A at 65 °C, and 340 A at 70 °C; that thermal curve matters if the breaker lives in a hot enclosure or next to other heat sources. The basic switch assembly is order code 3VA2340-7HL32-0AA0. A trip indicator is present, and the breaker includes no voltage-trigger or communication function — it's a straight line-protection device, not a power-monitoring unit. Maximum power loss is 98.5 W at rated load — factor that into enclosure ventilation if the panel is tight.

Frequently asked questions

How do I get current pricing and availability for 3VA2340-7HL32-0BL0?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.

What are the key interrupting ratings for 3VA2340-7HL32-0BL0?

330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 7.5 kA at 690 V.

What auxiliary switches are fitted on 3VA2340-7HL32-0BL0?

Two auxiliary switches, one trip alarm switch, and one electrical alarm switch (HQ type), plus an undervoltage release.

What is the continuous current rating of 3VA2340-7HL32-0BL0 at elevated temperatures?

400 A up to 50 °C, then derates to 385 A at 55 °C, 370 A at 60 °C, 355 A at 65 °C, and 340 A at 70 °C.

MPN
3VA2340-7HL32-0BL0