Skip to main content
Siemens 3VA2340-7HL32-0DA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2340-7HL32-0DA0 SENTRON MCCB, 400 A, 3-Pole, Line

MPN3VA2340-7HL32-0DA0

Siemens SENTRON 3VA2340-7HL32-0DA0, molded case circuit breaker, 3-pole, 400 A continuous, line protection, undervoltage release, 330 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2340-7HL32-0DA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2340-7HL32-0AA0

Ratings

3VA2340-7HL32-0DA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C385 A
Current at 60 °C370 A
Current at 65 °C355 A
Current at 70 °C340 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.98.5 W

Protection & Trip Unit

3VA2340-7HL32-0DA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2340-7HL32-0DA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2340-7HL32-0DA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2340-7HL32-0DA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2340-7HL32-0DA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

What this MCCB carries

The Siemens SENTRON 3VA2340-7HL32-0DA0 is a 3-pole molded case circuit breaker rated for 400 A continuous current at 40 °C through 50 °C, with a slight thermal derating curve down to 340 A at 70 °C. Its interrupting capacity hits 330 kA at 240 V AC, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 7.5 kA at 690 V — meaning it can handle high-fault utility feeds or transformer secondaries without cascading upstream. This is a line-protection design (not a motor-protective breaker), so it's intended for feeder and distribution panels where you need selectivity and high short-circuit withstand. The built-in undervoltage release (UVR) lets you trip the breaker on loss of control voltage — common in emergency-stop or undervoltage protection schemes. Dimensions are 248 mm high, 138 mm wide, 110 mm deep — fits standard MCCB mounting footprints in switchboards or enclosures. Maximum power loss at rated current is 98.5 W, which matters for thermal management inside a sealed panel.

Frequently asked questions

What is the interrupting capacity of 3VA2340-7HL32-0DA0 at 415 V?

At 415 V AC the interrupting capacity is 242 kA, matching the rating at 440 V. At 240 V it reaches 330 kA, and at 690 V it drops to 7.5 kA.

Does 3VA2340-7HL32-0DA0 include an undervoltage release?

Yes, it is equipped with an undervoltage release (UVR) as the auxiliary release, allowing the breaker to trip on loss of control voltage.

Where can I buy 3VA2340-7HL32-0DA0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for volume or project needs.

MPN
3VA2340-7HL32-0DA0