Skip to main content
Siemens 3VA2340-7HL32-0JA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2340-7HL32-0JA0 SENTRON MCCB, 400 A, 3-Pole, Shun

MPN3VA2340-7HL32-0JA0

Siemens SENTRON 3VA2340-7HL32-0JA0, molded case circuit breaker, 3-pole, 400 A, line protection, with shunt trip (STL), 110 mm depth, 138 mm width, 248 mm height.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2340-7HL32-0JA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2340-7HL32-0AA0
3VA2340-7HL32-0JA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C385 A
Current at 60 °C370 A
Current at 65 °C355 A
Current at 70 °C340 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.96 W
3VA2340-7HL32-0JA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2340-7HL32-0JA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2340-7HL32-0JA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2340-7HL32-0JA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2340-7HL32-0JA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

Its interrupting capacity reaches 330 kA at 240 V AC, 242 kA at 415/440 V, 187 kA at 500 V, and 7.5 kA at 690 V — so it handles high-fault scenarios typical of large transformer-fed switchboards or motor control centers without cascading upstream. Thermal derating is published from 40 °C to 70 °C: the breaker holds full 400 A up to 50 °C, then drops to 385 A at 55 °C, 370 A at 60 °C, 355 A at 65 °C, and 340 A at 70 °C — essential for sizing in warm enclosures or near heat sources.

The breaker measures 110 mm deep, 138 mm wide, and 248 mm tall — fits standard MCCB panel cutouts and busbar spacing for 3-pole 400 A frames. It includes a factory-installed shunt trip (STL) release for remote tripping via a control voltage, but no auxiliary switch or ground-fault module — those are add-on options if needed.

The base switch variant is 3VA2340-7HL32-0AA0; the -0JA0 suffix adds the shunt trip.

Frequently asked questions

Where can I buy 3VA2340-7HL32-0JA0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is 3VA2340-7HL32-0JA0's listed depth?

The depth is 110 mm (4.33 in).

What is 3VA2340-7HL32-0JA0's listed width?

The width is 138 mm (5.43 in).

Will 3VA2340-7HL32-0JA0 drop into a panel specified around 3VA2116-5HL32-0AK0 without rewiring?

No — the 3VA2340 frame is physically larger (138 mm wide vs the 3VA2116's 105 mm) and rated for 400 A vs 160 A, so it will not fit the same cutout or busbar spacing without panel modifications.

MPN
3VA2340-7HL32-0JA0