Skip to main content
Siemens 3VA2340-7JP42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2340-7JP42-0AA0 SENTRON MCCB, 400 A, 4-Pole, ETU5

MPN3VA2340-7JP42-0AA0
Active

Siemens SENTRON 3VA series, Molded case circuit breaker, 3VA2340-7JP42-0AA0, 400 A, 4-pole, ETU550 electronic trip unit, interrupting capacity 330 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2340-7JP42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA2340-7JP42-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C375 A
Current at 60 °C350 A
Current at 65 °C325 A
Current at 70 °C300 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.96 W

Protection & Trip Unit

3VA2340-7JP42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
Overcurrent protection functionLSI
Ground-fault monitoringWithout

Construction & Connection

3VA2340-7JP42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2340-7JP42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2340-7JP42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2340-7JP42-0AA0 — Mechanical
ParameterValue
Height248 mm
Width184 mm
Depth110 mm
Height (in)9.76 in
Width (in)7.24 in
Depth (in)4.33 in

Product details

This is a Siemens SENTRON 3VA molded case circuit breaker, order code 3VA2340-7JP42-0AA0. It's a 4-pole, 400 A continuous-rated breaker (at 40 °C) with an ETU550 electronic trip unit, built for line protection in distribution panels. The interrupting capacity hits 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 7.5 kA at 690 V — so it handles high-fault service entrances and downstream coordination without breaking a sweat. Rated insulation voltage is 800 V, and it carries communication onboard for integration into a monitored system.

What the ratings mean for your panel

The 400 A continuous rating holds at 40, 45, and 50 °C — no derating needed in a typical ventilated enclosure. At 55 °C it drops to 375 A, at 60 °C to 350 A, at 65 °C to 325 A, and at 70 °C to 300 A. If your gear is in a hot mezzanine or unvented cabinet, that derating curve is what decides whether this frame size works or you step up. The ETU550 trip unit gives you adjustable neutral protection — set it OFF or from 20% to 100% of the phase rating. That matters for panels feeding unbalanced loads or where you need to coordinate with downstream GFCI devices. No undervoltage release or ground-fault monitoring on this variant, so if those are spec'd, you're looking at a different 3VA option. Front-face protection is IP40 — fine inside a closed panel, but not for washdown or outdoor exposure without an additional enclosure. Operating temperature range is -25 °C to 70 °C; storage from -40 °C to 80 °C.

Panel fit and dimensions

The breaker measures 110 mm deep, 184 mm wide, and 248 mm tall. That's a 4-pole frame that needs 7.24 inches of DIN-rail width and 9.76 inches of vertical clearance. No trip indicator on the front, so plan for a separate status indication if your panel requires visual confirmation of tripped state.

Frequently asked questions

What is the interrupting capacity of this MCCB at different voltages?

The interrupting capacity is 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 7.5 kA at 690 V. That covers most industrial service-entrance and distribution applications.

What trip unit does this breaker use?

It uses the ETU550 electronic trip unit with adjustable neutral protection (OFF or 20% to 100%). No undervoltage release or ground-fault monitoring is included on this variant.

Where can I buy 3VA2340-7JP42-0AA0 and how is it quoted?

This breaker is sourced through independent distribution channels. Submit an RFQ for current pricing and availability — quotes are confirmed at order time with no minimum quantity restrictions.

MPN