Skip to main content
Siemens 3VA2340-7JQ32-0AA0 — Molded Case Circuit Breakers (MCCB)

3VA2340-7JQ32-0AA0 SENTRON MCCB, 400 A, 3-Pole, ETU560, 330

MPN3VA2340-7JQ32-0AA0
Active

Siemens SENTRON 3VA2 molded case circuit breaker, 3VA2340-7JQ32-0AA0, 3-pole, 400 A, ETU560 electronic trip unit, 330 kA at 240 V, line protection.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2340-7JQ32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2340-7JQ32-0AA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C375 A
Current at 60 °C350 A
Current at 65 °C325 A
Current at 70 °C300 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.96 W
3VA2340-7JQ32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560
Overcurrent protection functionLSIG
Ground-fault monitoringSummation current formation L-conductor
3VA2340-7JQ32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2340-7JQ32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2340-7JQ32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2340-7JQ32-0AA0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

Breaking capacity hits 330 kA at 240 V and 242 kA at 415 V, dropping to 7.5 kA at 690 V — that SCCR headroom covers transformer secondaries and large motor branch circuits without cascading upstream breakers. The ETU560 release supports adjustable N-conductor protection (OFF, 20% to 160%).

For a 40 °C panel, no derating needed — but if the enclosure runs hot from adjacent drives or transformers, factor the curve. The 3-pole frame mounts on a standard backplate or DIN rail adapter; front IP40 keeps out tools and dust in a closed cabinet. Maximum power loss is 96 W at rated current — budget that heat into the enclosure ventilation.

Frequently asked questions

What trip unit does this MCCB use?

The ETU560 electronic trip unit with adjustable N-conductor protection (OFF, 20% to 160%) and ground-fault monitoring via summation current on the L-conductor.

MPN
3VA2340-7JQ32-0AA0