Skip to main content
Siemens 3VA2440-0MN32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2440-0MN32-0AA0 SENTRON MCCB, 400 A, 440 kA at 41

MPN3VA2440-0MN32-0AA0
Active

Siemens SENTRON 3VA2440-0MN32-0AA0, molded case circuit breaker, 3-pole, 400 A, ETU350M electronic release, 440 kA at 415 V, motor protection design.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2440-0MN32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2440-0MN32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C400 A
Current at 60 °C400 A
Current at 65 °C400 A
Current at 70 °C400 A
Switching capacity classE
Breaking capacity at 415 V440 kA
Breaking capacity at 690 V187 kA
Power loss, max.63.5 W
3VA2440-0MN32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2440-0MN32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2440-0MN32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2440-0MN32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2440-0MN32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

MCCB with real headroom for motor circuits

The Siemens SENTRON 3VA2440-0MN32-0AA0 is a 3-pole molded case circuit breaker rated for 400 A continuous current, with a breaking capacity of 440 kA at 415 V — that's the kind of short-circuit rating that lets you place this breaker close to the transformer without worrying about cascading failures upstream. It's designed specifically for motor protection, so the ETU350M electronic release gives you adjustable trip classes of 10A, 10E, and 20E, meaning you can dial in the overload curve to match the starting characteristics of your motor load — pump, conveyor, or compressor — without nuisance tripping on inrush.

Sizing and thermal performance

That's flat derating across the typical panel temperature range — you don't have to oversize the frame just because the enclosure runs hot. That storage range matters if you're staging spares in an unheated warehouse — it won't degrade sitting through a cold winter.

That's a standard MCCB form factor for the 400 A frame class — it'll drop into a typical DIN-rail or panel-mount arrangement without surprises. The width is the critical dimension for multi-breaker lineups; 138 mm per pole set means you can calculate your backpanel real estate in advance.

Frequently asked questions

Where can I buy 3VA2440-0MN32-0AA0 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote.

What is the breaking capacity of 3VA2440-0MN32-0AA0?

It is rated 440 kA at 415 V and 187 kA at 690 V, giving substantial short-circuit withstand for motor branch circuits.

What trip classes are available on this MCCB?

The ETU350M electronic release offers adjustable trip classes 10A, 10E, and 20E, letting you match the overload curve to motor starting characteristics.

Does this breaker include phase failure protection?

Yes, phase failure detection is built in — it will trip on loss of a phase to prevent motor single-phasing.

MPN