Siemens 3VA2440-0MS32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2440-0MS32-0AA0 SENTRON MCCB, 400 A, 440 kA at 41

MPN3VA2440-0MS32-0AA0
Active

Siemens SENTRON 3VA2440-0MS32-0AA0, molded case circuit breaker, 400 A, 3-pole, ETU310M electronic trip unit, 440 kA at 415 V, motor protection design.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2440-0MS32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2440-0MS32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C400 A
Current at 60 °C400 A
Current at 65 °C400 A
Current at 70 °C400 A
Switching capacity classE
Breaking capacity at 415 V440 kA
Breaking capacity at 690 V187 kA
Power loss, max.63.5 W
3VA2440-0MS32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU310M
Overcurrent protection functionI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2440-0MS32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2440-0MS32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2440-0MS32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2440-0MS32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

The Siemens SENTRON 3VA2440-0MS32-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated for 400 A continuous current, designed specifically for motor protection with an ETU310M electronic overcurrent release. Its interrupting capacity hits 440 kA at 415 V and 187 kA at 690 V, meaning it can clear a massive fault without the arc flash escalating — critical for high-fault panels feeding motor control centers. The adjustable trip range spans 600 A to 5 200 A, so you can dial it in for the motor's locked-rotor current without swapping the breaker body.

Mounts in a standard panel on a DIN rail or bolted bus — footprint is 138 mm wide, 248 mm tall, 110 mm deep, which is a common 3-pole frame size for this class. Front face is IP40 rated, fine for clean indoor switchgear; no washdown protection, so keep it out of wet environments. Operates from -25 °C to 70 °C ambient, and the current rating holds at 400 A all the way up to 70 °C — no derating needed in a warm panel.

What the trip unit means for the job

No undervoltage release, no phase-failure detection, no communication function built in — this is a standalone thermal-magnetic replacement for a motor starter feeder.

Frequently asked questions

Where can I buy 3VA2440-0MS32-0AA0?

This part is sourced to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is the breaking capacity of this MCCB?

440 kA at 415 V and 187 kA at 690 V, making it suitable for high-fault-current panels.

What are the mounting dimensions?

Width 138 mm, height 248 mm, depth 110 mm — a standard 3-pole frame size.

Does this breaker include ground-fault protection?

No, this variant ships without ground-fault monitoring (version 'Without').

MPN
3VA2440-0MS32-0AA0