Siemens 3VA2440-5HL32-0DC0 SENTRON MCCB, 400 A, 3-Pole, ETU3

MPN3VA2440-5HL32-0DC0

Siemens SENTRON 3VA2440-5HL32-0DC0, molded case circuit breaker, 3-pole, 400 A, ETU320 electronic trip unit, line protection, with undervoltage release and 2 auxiliary switches HQ.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2440-5HL32-0DC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2440-5HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA2440-5HL32-0DC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C384 A
Current at 60 °C376 A
Current at 65 °C368 A
Current at 70 °C360 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V17 kA
Power loss, max.66 W
3VA2440-5HL32-0DC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2440-5HL32-0DC0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2440-5HL32-0DC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2440-5HL32-0DC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2440-5HL32-0DC0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

400 A MCCB with ETU320 — what the ratings mean for panel fit

The Siemens 3VA2440-5HL32-0DC0 is a SENTRON molded case circuit breaker (MCCB) rated for 400 A continuous current (Iu) across a 3-pole configuration, making it the main feeder or large-motor protection in a 400 V industrial distribution panel. The ETU320 electronic trip unit gives you adjustable long-time, short-time, instantaneous, and ground-fault protection curves — not a fixed thermal-magnetic response, so coordination studies actually mean something downstream. Breaking capacity is voltage-dependent: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V. At 415 V — the common European industrial supply — 121 kA SCCR means this breaker clears a bolted fault without upstream fuses needing to open, provided the panel bus bracing holds. That is a high-interrupting rating for a 400 A frame; you are not forced into a current-limiting fuse coordination. Thermal derating is published per degree: full 400 A up to 50 °C, then 384 A at 55 °C, 376 A at 60 °C, 368 A at 65 °C, and 360 A at 70 °C. If the panel ambient runs at 55 °C, you lose 16 A of headroom — factor that into the load schedule before committing the BOM line.

Undervoltage release and auxiliary switching

This variant ships with an undervoltage release (UVR) fitted — the basic switch is order code 3VA2440-5HL32-0AA0, and the integrated auxiliary trip is 3VA9608-0BB25. The UVR drops the breaker on loss of control voltage, which is standard for emergency-stop circuits or undervoltage protection on motor feeders. Two auxiliary switches (HQ type) are built in for status feedback to a PLC or remote indication panel. Rated insulation voltage Ui is 800 V, so the breaker is rated for 690 V systems without derating the internal creepage distances. Maximum power loss at rated current is 66 W — plan ventilation accordingly if the MCCB is enclosed in a low-volume pull-box rather than a ventilated switchboard.

Frequently asked questions

How do I get current pricing and availability for 3VA2440-5HL32-0DC0?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels — no stock count or price is published here.

What is the breaking capacity of 3VA2440-5HL32-0DC0 at 415 V?

121 kA at 415 V and 440 V, 187 kA at 240 V, 75.6 kA at 500 V, and 17 kA at 690 V.

What trip unit does the 3VA2440-5HL32-0DC0 use?

The ETU320 electronic trip unit, which provides adjustable long-time, short-time, instantaneous, and ground-fault protection curves.

Does the 3VA2440-5HL32-0DC0 include an undervoltage release?

Yes, it is fitted with an undervoltage release (UVR) as standard. The basic switch without UVR is order code 3VA2440-5HL32-0AA0.