Skip to main content
Siemens 3VA2440-5HL32-0JL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2440-5HL32-0JL0 SENTRON MCCB, 400 A, 3-Pole, 187

MPN3VA2440-5HL32-0JL0

Siemens SENTRON molded case circuit breaker, 3VA2440-5HL32-0JL0, 3-pole, 400 A rated continuous current, breaking capacity 187 kA at 240 V, with ETU320 electronic trip unit and shunt trip release.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2440-5HL32-0JL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2440-5HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22
3VA2440-5HL32-0JL0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C384 A
Current at 60 °C376 A
Current at 65 °C368 A
Current at 70 °C360 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V17 kA
Power loss, max.63.5 W
3VA2440-5HL32-0JL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2440-5HL32-0JL0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2440-5HL32-0JL0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4
3VA2440-5HL32-0JL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2440-5HL32-0JL0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

The Siemens SENTRON 3VA2440-5HL32-0JL0 is a 3-pole molded case circuit breaker (MCCB) rated for 400 A continuous current (Iu) at 40 °C ambient, with an insulation voltage (Ui) of 800 V. It carries a breaking capacity of 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V — figures that define its fault-interrupting capability across common distribution voltages.

The 400 A rating holds flat from 40 °C to 50 °C, then derates to 384 A at 55 °C, 376 A at 60 °C, 368 A at 65 °C, and 360 A at 70 °C. A shunt trip release (STL) is built in for remote tripping. Power loss is rated at 63.5 W maximum. In a densely packed panel, that heat must be managed — allow clearance and ventilation per Siemens mounting guidelines.

Physical integration

Dimensions: 248 mm height, 138 mm width, 110 mm depth. The 3-pole footprint is standard for this current class; panel cutout and busbar spacing should match Siemens SENTRON 3VA family mounting patterns.

Frequently asked questions

Where can I buy 3VA2440-5HL32-0JL0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of this MCCB at 415 V?

At 415 V, the breaking capacity is 121 kA.

Does this breaker include a shunt trip?

Yes, the design of the auxiliary release is a shunt trip (STL), allowing remote tripping.

MPN
3VA2440-5HL32-0JL0