Skip to main content
Siemens 3VA2440-5HN32-0CH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2440-5HN32-0CH0 SENTRON MCCB, 400 A, 3-Pole, 187

MPN3VA2440-5HN32-0CH0

Siemens SENTRON 3VA2440-5HN32-0CH0, molded case circuit breaker, 3-pole, 400 A, 187 kA interrupting at 240 V, line protection design with undervoltage release and auxiliary switches.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2440-5HN32-0CH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2440-5HN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA2440-5HN32-0CH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C400 A
Current at 60 °C400 A
Current at 65 °C400 A
Current at 70 °C400 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V9 kA
Power loss, max.66 W

Protection & Trip Unit

3VA2440-5HN32-0CH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2440-5HN32-0CH0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2440-5HN32-0CH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA2440-5HN32-0CH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2440-5HN32-0CH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

What this MCCB carries and where it fits

The Siemens SENTRON 3VA2440-5HN32-0CH0 is a 3-pole molded case circuit breaker rated for 400 A continuous at 40 °C through 70 °C — no derating needed across that full ambient span, which simplifies panel design in warm enclosures or near heat sources. Interrupting capacity reaches 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 9 kA at 690 V — figures that cover most industrial service-entrance and distribution applications, though the 690 V number means this frame is not a primary choice for 690 V switchgear. Designed for line protection, it ships with an undervoltage release (UVR) and a complement of two auxiliary switches plus one trip-alarm switch (HQ) — enough for remote status and undervoltage lockout without adding external relays.

Mounting and panel fit

Dimensions are 248 mm high, 138 mm wide, 110 mm deep — a standard MCCB footprint that fits most 400 A panelboards and distribution blocks without gland-plate conflicts. Maximum power loss is 66 W; account for that in enclosure thermal calculations if the breaker is in a sealed, non-ventilated cabinet alongside other heat sources.

Frequently asked questions

Does this MCCB include an undervoltage release?

Yes, it comes with an undervoltage release (UVR) plus two auxiliary switches and one trip-alarm switch (HQ) factory-installed.

MPN
3VA2440-5HN32-0CH0