Siemens 3VA2440-5HN32-0LJ0 Circuit Breaker, 400A, 55kA @ 415

MPN3VA2440-5HN32-0LJ0

Siemens 3VA2 series, IEC frame 630, breaking capacity class M, 3-pole circuit breaker, 400 A, Icu=55 kA @ 415 V, ETU350 LSI trip unit, universal release 24 V DC, 2 auxiliary switches + 1 trip alarm switch.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Product details

The Siemens 3VA2440-5HN32-0LJ0 is a 3-pole IEC frame 630 circuit breaker in the 3VA2 series, rated for line protection with an ETU350 LSI trip unit. Its breaking capacity class M delivers Icu=55 kA at 415 V, which means it can safely interrupt fault currents up to that level without upstream cascading — a key figure for selectivity studies on a 400 V distribution board feeding motor control centers or refrigeration compressor banks.

Rated In=400 A, with overload protection Ir adjustable from 160 A to 400 A, short-circuit protection Isd from 1.5 to 10 x Ir, and instantaneous pickup Ii fixed at 12 x In. The universal release (UNI) operates on 24 V DC, and the breaker ships with a nut keeper kit plus two auxiliary switches (HP) and one trip alarm switch (HP) — enough auxiliary contacts for remote status feedback on a PLC input card without adding a separate block.

Frequently asked questions

Where can I buy 3VA2440-5HN32-0LJ0 and get a price?

The part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA2440-5HN32-0LJ0?

Icu=55 kA at 415 V (breaking capacity class M), which is the maximum fault current the breaker can safely interrupt at that voltage.

What trip unit does this breaker use?

An ETU350 LSI electronic trip unit with adjustable overload (Ir=160-400 A), short-delay (Isd=1.5-10 x Ir), and instantaneous (Ii=12 x In) protection curves.