MCCB for 400 A feeder protection
Its interrupting capacity reaches 242 kA at 240 V AC, 187 kA at 415/440 V, and 121 kA at 500 V — figures that govern its placement in high-fault panels where selective coordination with downstream breakers is required.
Thermal derating and operating envelope
Above that, derate linearly: 384 A at 55 °C, 376 A at 60 °C, 368 A at 65 °C, and 360 A at 70 °C.
Auxiliary and release configuration
The integrated auxiliary trip is order code 3VA9608-0BB11. A trip indicator is present. Latching endurance is rated at 15,000 operations.