400 A MCCB with ETU320 — interrupting capacity and thermal derating
The breaker carries the full 400 A up to 50 °C ambient; above that, derate to 384 A at 55 °C, 376 A at 60 °C, 368 A at 65 °C, and 360 A at 70 °C (–). Maximum power loss is 66 W.
Panel integration — dimensions and mounting
Interrupting ratings at system voltages
Rated short-circuit breaking capacity: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 40 kA at 690 V (–). These values cover most industrial distribution voltages up to 690 V.