Skip to main content
Siemens 3VA2440-6HL32-0CL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2440-6HL32-0CL0 SENTRON MCCB, 400A, 3-Pole, ETU32

MPN3VA2440-6HL32-0CL0

Siemens SENTRON 3VA2440-6HL32-0CL0, molded case circuit breaker, 3-pole, 400 A, ETU320 line protection trip unit, 242 kA at 240 V, with undervoltage release and auxiliary switches.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2440-6HL32-0CL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2440-6HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22
3VA2440-6HL32-0CL0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C384 A
Current at 60 °C376 A
Current at 65 °C368 A
Current at 70 °C360 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V40 kA
Power loss, max.66 W
3VA2440-6HL32-0CL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2440-6HL32-0CL0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2440-6HL32-0CL0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4
3VA2440-6HL32-0CL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2440-6HL32-0CL0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

The 242 kA breaking capacity at 240 V (187 kA at 415 V, 121 kA at 500 V, 40 kA at 690 V) gives substantial SCCR headroom for high-fault installations — the breaker clears faults up to that level without cascading upstream, which matters when coordinating downstream feeders in a main distribution panel. Thermal derating is published across the full operating range: the breaker carries a full 400 A up to 50 °C ambient, then steps down to 384 A at 55 °C, 376 A at 60 °C, 368 A at 65 °C, and 360 A at 70 °C. For a panel builder sizing a main breaker in a non-climate-controlled enclosure, the 55 °C column is often the real-world rating — 384 A continuous, not the nameplate 400 A. The integrated undervoltage release (UVR) allows a safety circuit to trip the breaker on loss of control voltage — a common requirement for emergency-stop chains and power-management systems.

Lifecycle and sourcing — current production, quoted to order

The 3VA2440-6HL32-0CL0 carries the SENTRON branding and is designed to IEC 60947-2 and UL 489 standards. The ETU320 trip unit is field-configurable for LSI protection curves, which gives the specifying engineer flexibility to adjust long-time, short-time, and instantaneous pickup thresholds without swapping hardware.

Panel integration — footprint and mounting

Dimensions are 248 mm height × 138 mm width × 110 mm depth. The 138 mm width fits a standard 3-pole MCCB cutout in a distribution board. Maximum power loss is 66 W, which should be factored into the enclosure thermal budget — particularly when multiple breakers are ganged in a sealed cabinet. The part is not conformally coated as standard, so for marine or high-humidity environments, verify the enclosure rating separately.

Frequently asked questions

Where can I buy the 3VA2440-6HL32-0CL0 and get a price?

The part is sourced through independent distribution channels and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.

What is the breaking capacity of this MCCB at different voltages?

Breaking capacity is 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 40 kA at 690 V. These are the maximum fault currents the breaker can safely interrupt at each voltage level.

What trip unit does the 3VA2440-6HL32-0CL0 use?

It uses the ETU320 electronic trip unit configured for line protection (LSI curves). The trip unit is field-configurable for long-time, short-time, and instantaneous pickup settings.

Does this breaker include an undervoltage release?

Yes, it includes an integrated undervoltage release (UVR) that trips the breaker when control voltage is lost — suitable for safety circuits and emergency-stop chains.

MPN
3VA2440-6HL32-0CL0