Skip to main content
Siemens 3VA2440-6HL32-0HA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2440-6HL32-0HA0 SENTRON MCCB, 400A, 242kA at 240V

MPN3VA2440-6HL32-0HA0

Siemens SENTRON 3VA2440-6HL32-0HA0, molded case circuit breaker, line protection, 3-pole, 400 A at 40 °C, breaking capacity 242 kA at 240 V, ETU320 release, shunt trip.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2440-6HL32-0HA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2440-6HL32-0AA0
3VA2440-6HL32-0HA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C384 A
Current at 60 °C376 A
Current at 65 °C368 A
Current at 70 °C360 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V40 kA
Power loss, max.63.5 W
3VA2440-6HL32-0HA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2440-6HL32-0HA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2440-6HL32-0HA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2440-6HL32-0HA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2440-6HL32-0HA0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

At 415 V and 440 V the rating holds at 187 kA, dropping to 121 kA at 500 V and 40 kA at 690 V. For a 400 A frame, these numbers place it in the high-interrupting category, suited for large transformer secondaries or bus-tie applications where fault current can exceed 100 kA. Thermal derating is modest: the breaker carries the full 400 A up to 50 °C ambient, then drops to 384 A at 55 °C, 376 A at 60 °C, 368 A at 65 °C, and 360 A at 70 °C.

Trip unit, release, and auxiliary options — what is and is not inside

The supplied basic switch is 3VA2440-6HL32-0AA0. If your application requires undervoltage protection or remote status feedback, you will need a different suffix or field-installable accessory. The breaker has a voltage-trigger function (yes) but no trip indicator. Mechanical endurance is rated at 15,000 operations — typical for a 400 A frame used in infrequent switching (main disconnect or backup, not motor-start duty).

The 110 mm depth is shallower than many 400 A MCCBs, which helps in shallow enclosures.

Frequently asked questions

Where can I buy the 3VA2440-6HL32-0HA0 and how is it quoted?

The 3VA2440-6HL32-0HA0 is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of the 3VA2440-6HL32-0HA0 at different voltages?

At 240 V the breaking capacity is 242 kA; at 415 V and 440 V it is 187 kA; at 500 V it is 121 kA; and at 690 V it is 40 kA.

Does the 3VA2440-6HL32-0HA0 include an undervoltage release or ground-fault protection?

No — this variant has no undervoltage release, no ground-fault monitoring, no communication function, and no phase-failure detection. It ships with a shunt trip (STL) auxiliary release and an ETU320 overcurrent release.

What are the physical dimensions of the 3VA2440-6HL32-0HA0?

Height is 248 mm, width is 138 mm, and depth is 110 mm.

MPN
3VA2440-6HL32-0HA0