Skip to main content
Siemens 3VA2440-6HN32-0CA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2440-6HN32-0CA0 SENTRON MCCB, 400 A, 242 kA

MPN3VA2440-6HN32-0CA0

Siemens SENTRON 3VA2440-6HN32-0CA0, molded case circuit breaker, 3-pole, 400 A, 242 kA at 240 V, line protection, ETU350 overcurrent release, undervoltage release.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2440-6HN32-0CA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2440-6HN32-0AA0
3VA2440-6HN32-0CA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C384 A
Current at 60 °C376 A
Current at 65 °C368 A
Current at 70 °C360 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V40 kA
Power loss, max.66 W
3VA2440-6HN32-0CA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
3VA2440-6HN32-0CA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2440-6HN32-0CA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2440-6HN32-0CA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2440-6HN32-0CA0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

What this 400 A MCCB carries

That 400 A holds flat from 40 °C up to 50 °C; above that it derates to 384 A at 55 °C, 376 A at 60 °C, 368 A at 65 °C, and 360 A at 70 °C. For a panel builder, that means the breaker can sit in a warm enclosure without losing headroom until the ambient passes 50 °C. Breaking capacity runs 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 40 kA at 690 V.

The 3VA2440-6HN32-0CA0 measures 248 mm high by 138 mm wide by 110 mm deep.

What the ETU350 release does

No communication function, no phase-failure detection, no voltage trigger. The trip indicator is also absent, so fault isolation relies on the breaker position or a separate auxiliary contact (not included).

Frequently asked questions

How do I get pricing and availability for 3VA2440-6HN32-0CA0?

Submit an RFQ through the storefront. Availability and current pricing are confirmed at quote time through independent distribution channels.

What are the key ratings for 3VA2440-6HN32-0CA0?

Rated continuous current 400 A, breaking capacity 242 kA at 240 V, 187 kA at 415 V, 121 kA at 500 V, 40 kA at 690 V. Dimensions 248 x 138 x 110 mm.

Does 3VA2440-6HN32-0CA0 include an undervoltage release?

Yes, it ships with an integrated undervoltage release (UVR) as the auxiliary release. The base switch without UVR is 3VA2440-6HN32-0AA0.

MPN
3VA2440-6HN32-0CA0