Skip to main content
Siemens 3VA2440-6HN32-0KC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2440-6HN32-0KC0 SENTRON MCCB, 400 A, 4800 A frame

MPN3VA2440-6HN32-0KC0

Siemens SENTRON 3VA2440-6HN32-0KC0, 3-pole molded case circuit breaker, 400 A continuous, 4800 A frame, line protection, with shunt trip (STL) and 2 HQ auxiliary switches.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2440-6HN32-0KC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2440-6HN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2440-6HN32-0KC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C400 A
Current at 60 °C400 A
Current at 65 °C400 A
Current at 70 °C400 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V9 kA
Power loss, max.63.5 W

Protection & Trip Unit

3VA2440-6HN32-0KC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2440-6HN32-0KC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2440-6HN32-0KC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2440-6HN32-0KC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2440-6HN32-0KC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

What this MCCB delivers

The Siemens 3VA2440-6HN32-0KC0 is a 3-pole SENTRON molded case circuit breaker rated for 400 A continuous current across its full operating temperature range of -25 °C to 70 °C, meaning no derating is needed even in a hot panel — a real advantage when the enclosure sits near a furnace or in a non-climate-controlled plant area. The frame is sized for 4800 A, giving headroom for high-fault installations. Breaking capacity reaches 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 9 kA at 690 V — figures that cover most industrial low-voltage distribution systems. Short-time withstand is 5 kA for 1 s, which supports selective coordination downstream.

Built-in accessories and integration

This MCCB ships with a shunt trip (STL) for remote tripping and two HQ auxiliary switches for status feedback — both factory-fitted, so no field wiring of add-on modules. The basic switch variant is 3VA2440-6HN32-0AA0. No undervoltage release or ground-fault monitoring is included. Dimensions are 248 mm high, 138 mm wide, 110 mm deep — a standard SENTRON 3VA footprint that fits existing panel cutouts and busbar layouts without rework. Maximum power loss is 63.5 W, which should be factored into enclosure thermal calculations.

Frequently asked questions

Where can I buy 3VA2440-6HN32-0KC0 and what is the lead time?

This part is sourced and quoted to order against an RFQ through our independent distribution network; availability and current pricing are confirmed at quote time.

What are the key ratings for 3VA2440-6HN32-0KC0?

Continuous current is 400 A across -25 °C to 70 °C with no derating. The frame is rated 4800 A. Breaking capacity ranges from 242 kA at 240 V down to 9 kA at 690 V. Short-time withstand is 5 kA for 1 s.

Will 3VA2440-6HN32-0KC0 drop into a panel specified around 3VA1110-5EE32-0LC0?

The 3VA2440 frame is physically larger — 248 mm high, 138 mm wide, 110 mm deep — while the 3VA1110 frame is smaller. Panel cutouts and busbar spacing designed for the 3VA1110 will not accommodate this MCCB without mechanical rework.

MPN