It carries a 242 kA interrupting capacity at 240 V, stepping down to 187 kA at 415/440 V and 121 kA at 500 V, with a 9 kA floor at 690 V. The ETU850 electronic trip unit handles line protection duty with communication capability, making it a fit for main or feeder breakers in LV switchboards where selective coordination matters.
The 400 A rating at 70 °C means this breaker handles full load in a warm enclosure without downsizing — a common pain point with breakers that derate above 40 °C.