Siemens 3VA2440-7HL32-0AJ0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2440-7HL32-0AJ0 SENTRON MCCB, 400 A, 3-Pole

MPN3VA2440-7HL32-0AJ0

Siemens SENTRON 3VA2440-7HL32-0AJ0, 3-pole molded case circuit breaker, 400 A continuous rating, adjustable instantaneous trip 600–4800 A, breaking capacity 330 kA at 240 V AC, line protection design.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2440-7HL32-0AJ0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2440-7HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB11
3VA2440-7HL32-0AJ0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C400 A
Current at 60 °C400 A
Current at 65 °C400 A
Current at 70 °C400 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V9 kA
Power loss, max.63.5 W
3VA2440-7HL32-0AJ0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2440-7HL32-0AJ0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2440-7HL32-0AJ0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA2440-7HL32-0AJ0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2440-7HL32-0AJ0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

The Siemens SENTRON 3VA2440-7HL32-0AJ0 is a 3-pole molded case circuit breaker rated for 400 A continuous current across its full ambient range of 40 °C to 70 °C — no derating needed up to the top of that band. That flat thermal curve is the headline feature for panel builders: it simplifies coordination in a warm enclosure where other breakers would force a frame size bump. The adjustable instantaneous trip range spans 600 A to 4800 A, letting you dial in selectivity with downstream devices without swapping the breaker. At 240 V the interrupting rating hits 330 kA; at 415 V and 440 V it holds at 242 kA, dropping to 187 kA at 500 V and 9 kA at 690 V. Maximum power loss is 63.5 W — relevant for thermal management inside a sealed panel. The base order code is 3VA2440-7HL32-0AA0; this -0AJ0 variant adds the specified auxiliary contact package.

The depth of 110 mm (4.33 in) is compact enough for shallow backpanel layouts; verify gland-plate clearance against the 248 mm height when mounting in a row with other breakers. The 70 °C operating ceiling matches the top of the flat derating curve, so the breaker delivers its full 400 A even in a hot enclosure near the top of a panel.

Frequently asked questions

Where can I buy 3VA2440-7HL32-0AJ0?

This part is available to quote against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — no stock count or lead-time number is published here, but the part is actively sourced.

What is the continuous current rating of this MCCB?

400 A continuous across the full ambient range of 40 °C to 70 °C — no derating required. The adjustable instantaneous trip range is 600 A to 4800 A.

What are the physical dimensions of 3VA2440-7HL32-0AJ0?

248 mm high × 138 mm wide × 110 mm deep (9.76 in × 5.43 in × 4.33 in). Standard 3-pole MCCB footprint for the 400 A class.

What breaking capacity does this breaker have at different voltages?

330 kA at 240 V AC, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 9 kA at 690 V. The 330 kA at 240 V is notably high for a 400 A frame — suitable for high-fault locations like transformer secondaries.

MPN
3VA2440-7HL32-0AJ0