Interrupting capacity is the headline number here: 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 9 kA at 690 V. At 415/440 V the 242 kA rating still provides substantial headroom for most industrial service entrances. Adjustable overload and short-circuit protection covers 600 A to 4800 A, with a trip indicator and voltage-trigger capability built in.
Footprint: 138 mm wide, 248 mm tall, 110 mm deep. The basic switch assembly is order code 3VA2440-7HL32-0AA0; the -0JH0 suffix adds the shunt trip and auxiliary switch complement. No ground-fault monitoring module is included (specified as "Without"). If GF protection is needed downstream, plan for a separate GF relay or a different variant.