Skip to main content
Siemens 3VA2440-8HK32-0AA0 — Molded Case Circuit Breakers (MCCB)

3VA2440-8HK32-0AA0 SENTRON MCCB, 400 A, 440 kA at 240 V

MPN3VA2440-8HK32-0AA0
Active

Siemens SENTRON 3VA2 molded case circuit breaker, 3-pole, 400 A rated, ETU340 electronic trip, 440 kA at 240 VAC.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2440-8HK32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA2440-8HK32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C400 A
Current at 60 °C400 A
Current at 65 °C400 A
Current at 70 °C400 A
Switching capacity classL
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V330 kA
Breaking capacity at 440 V330 kA
Breaking capacity at 500 V220 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.63.5 W

Protection & Trip Unit

3VA2440-8HK32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU340
Overcurrent protection functionELISA LI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2440-8HK32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2440-8HK32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2440-8HK32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2440-8HK32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

400 A, 440 kA — what it means on the line

The 3VA2440-8HK32-0AA0: This 3-pole SENTRON 3VA2 MCCB carries 400 A continuous at 40–70 °C with no derating — same output across the full ambient range. Breaking capacity hits 440 kA at 240 VAC, 330 kA at 415 V, and still delivers 220 kA at 500 V; at 690 V it holds 52.5 kA. That means it clears high-fault scenarios in industrial distribution without cascading upstream — line protection design for heavy plant feeds.

ETU340 trip unit — what it controls

The ETU340 electronic overcurrent release gives you adjustable long-time, short-time, and instantaneous pickup plus ground-fault protection — though this variant ships without ground-fault monitoring. No undervoltage release, no communication module, no voltage-trigger accessory. It's a straight line-protection MCCB: trip indicator absent, no auxiliary contacts on the base unit. Power loss at full load is 63.5 W — plan ventilation accordingly.

Panel fit — dimensions and mounting

Footprint: 138 mm wide, 248 mm tall, 110 mm deep. Bolts into a standard MCCB panel cutout — no DIN-rail mount, this is a fixed breaker. Verify the bus-bar spacing and lug kit compatibility when replacing a previous frame.

Frequently asked questions

What is 3VA2440-8HK32-0AA0's listed depth?

Listed depth is 110 mm (4.33 in).

What is 3VA2440-8HK32-0AA0's listed width?

Listed width is 138 mm (5.43 in).

MPN