The Siemens 3VA2440-8HN42-0AA0 is a SENTRON molded case circuit breaker (MCCB) rated for 400 A continuous at 40 °C, with a 4-pole configuration and an ETU350 electronic trip unit. Breaking capacity reaches 440 kA at 240 V, 330 kA at 415 V, and 53 kA at 690 V — sufficient for high-fault utility feeds or transformer secondaries. The line protection version omits ground-fault monitoring and communication functions; a motor-drive option is available for remote switching.
The ETU350 trip unit offers adjustable long-time (I²t) and instantaneous (Ii) protection: Ii is fixed at 4400 A (11x In), and the neutral protection is configurable OFF, 50%, or 100% of phase current.
Front-face protection is IP40, suitable for indoor enclosures. The optional motor drive (order separately) enables remote closing and tripping for automated feeder control.