Skip to main content
Siemens 3VA2450-0MN32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2450-0MN32-0AA0 SENTRON MCCB, 500 A, 3-Pole, ETU3

MPN3VA2450-0MN32-0AA0
Active

Siemens SENTRON 3VA2 molded case circuit breaker, 3VA2450-0MN32-0AA0, 500 A, 3-pole, ETU350M electronic trip unit, motor protection design, 440 kA breaking capacity at 415 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2450-0MN32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2450-0MN32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C500 A
Current at 45 °C500 A
Current at 50 °C500 A
Current at 55 °C495 A
Current at 60 °C490 A
Current at 65 °C485 A
Current at 70 °C480 A
Switching capacity classE
Breaking capacity at 415 V440 kA
Breaking capacity at 690 V187 kA
Power loss, max.99 W
3VA2450-0MN32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2450-0MN32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2450-0MN32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2450-0MN32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2450-0MN32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

The Siemens 3VA2450-0MN32-0AA0 is a 3-pole SENTRON molded case circuit breaker rated for 500 A continuous current at 40 °C, holding that full rating through 50 °C before derating starts — at 55 °C it carries 495 A, at 60 °C it carries 490 A, at 65 °C it carries 485 A, and at 70 °C it carries 480 A. That thermal profile matters when you pack breakers into a warm enclosure; you don't lose headroom until the ambient hits 55 °C. The limited short-time rating is 6 kA for 1 s, which supports selective coordination downstream.

Dimensions are 138 mm wide, 248 mm high, 110 mm deep — a standard 3-pole MCCB footprint for the SENTRON 3VA2 frame. No undervoltage release or shunt trip fitted as-delivered; those are add-on accessories.

Frequently asked questions

Where can I buy 3VA2450-0MN32-0AA0?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA2450-0MN32-0AA0?

440 kA at 415 V and 187 kA at 690 V, with a limited short-time rating of 6 kA for 1 s.

What trip classes does the ETU350M support?

Adjustable trip classes 10A, 10E, and 20E, plus phase failure detection — suited for motor protection applications.