Skip to main content
Siemens 3VA2450-5JP32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2450-5JP32-0AA0 MCCB, 500 A, 187 kA

MPN3VA2450-5JP32-0AA0
Active

Siemens SENTRON molded case circuit breaker, 3VA2450-5JP32-0AA0, 3-pole, 500 A rated at 40 °C, ETU550 electronic trip unit, 187 kA breaking capacity at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2450-5JP32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2450-5JP32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C500 A
Current at 45 °C500 A
Current at 50 °C500 A
Current at 55 °C477 A
Current at 60 °C455 A
Current at 65 °C432 A
Current at 70 °C410 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V9 kA
Power loss, max.99 W
3VA2450-5JP32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2450-5JP32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2450-5JP32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2450-5JP32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2450-5JP32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

The Siemens SENTRON 3VA2450-5JP32-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated 500 A continuous at 40 °C, with the ETU550 electronic trip unit onboard. It breaks up to 187 kA at 240 V, 121 kA at 415 V, and 9 kA at 690 V — so it handles high-fault service entrances and distribution main feeds without cascading upstream. The 500 A rating holds steady through 50 °C; above that it derates to 477 A at 55 °C and 410 A at 70 °C, which matters when the breaker sits in a warm enclosure next to other heat sources.

The ETU550 trip unit supports communication, so it can report status and trip events to a BMS or PLC — useful for remote monitoring on a main feeder.

Frequently asked questions

Where can I buy 3VA2450-5JP32-0AA0?

This part is sourced to order against an RFQ through independent distribution; availability and pricing are confirmed at quote time.

What is the breaking capacity of 3VA2450-5JP32-0AA0?

It breaks 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 9 kA at 690 V.

Does 3VA2450-5JP32-0AA0 have communication capability?

Yes, the ETU550 trip unit includes a communication function for remote monitoring.

MPN
3VA2450-5JP32-0AA0