Skip to main content
Siemens 3VA2450-5JP32-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2450-5JP32-0AH0 Circuit Breaker, 500A, 55kA @ 415

MPN3VA2450-5JP32-0AH0

Siemens 3VA2 series, IEC frame 630, 3-pole MCCB, 500 A, breaking capacity class M (Icu=55 kA @ 415 V), ETU550 LSI electronic trip unit, line protection.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Product details

The Siemens 3VA2450-5JP32-0AH0 is a 3-pole IEC frame 630 molded-case circuit breaker (MCCB) rated 500 A continuous, with a breaking capacity class M of Icu=55 kA at 415 V AC. The ETU550 electronic trip unit provides LSI protection: long-time (overload) adjustable from 200 A to 500 A, short-time (selective coordination) adjustable 0.6–10× In, and instantaneous fixed at 1.5–14× In. This makes the breaker suitable for feeder circuits where coordination with downstream devices matters, not just a simple thermal-magnetic cutoff.

What is on the nameplate — auxiliary switches and trip alarm

Factory-fitted on this variant: two changeover auxiliary switches (H configuration) and one changeover trip-alarm switch. That gives the panel builder or controls integrator remote status of the breaker position (open/closed) plus a separate signal when the breaker has tripped on fault — no need to add field-installed accessory kits for basic indication. The neutral conductor protection is optional via an external current transformer, up to 160 % of In, per the description.

Frequently asked questions

Where can I buy 3VA2450-5JP32-0AH0 and get a price?

This part is sourced through independent distribution and quoted to order against an RFQ. Submit a request for current availability and pricing; a confirmed quote will be provided at that time.

What is the breaking capacity of this breaker?

The 3VA2450-5JP32-0AH0 carries an Icu of 55 kA at 415 V AC, which is the class M breaking capacity for the 3VA2 IEC frame 630 series.

MPN
3VA2450-5JP32-0AH0