Skip to main content
Siemens 3VA2450-5KP42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2450-5KP42-0AA0 SENTRON MCCB, 500 A, 4-Pole, 187

MPN3VA2450-5KP42-0AA0
Active

Siemens SENTRON 3VA2450-5KP42-0AA0, molded case circuit breaker, 4-pole, 500 A rated continuous current, 187 kA interrupting capacity at 240 V AC, ETU850 electronic trip unit.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2450-5KP42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2450-5KP42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C500 A
Current at 45 °C500 A
Current at 50 °C500 A
Current at 55 °C477 A
Current at 60 °C455 A
Current at 65 °C432 A
Current at 70 °C410 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V9 kA
Power loss, max.99 W
3VA2450-5KP42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2450-5KP42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2450-5KP42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts0
3VA2450-5KP42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2450-5KP42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width184 mm
Depth110 mm
Height (in)9.76 in
Width (in)7.24 in
Depth (in)4.33 in

Product details

The Siemens SENTRON 3VA2450-5KP42-0AA0 is a 4-pole molded case circuit breaker (MCCB) rated for 500 A continuous current at 40 °C, with an ETU850 electronic trip unit covering an adjustable overload range from 750 A to 7 000 A. It delivers 187 kA interrupting capacity at 240 V AC, stepping down to 121 kA at 415/440 V, 75.6 kA at 500 V, and 9 kA at 690 V — enough headroom for most industrial service-entrance or feeder applications.

The 500 A continuous rating holds flat from 40 °C up to 50 °C, then derates to 477 A at 55 °C, 455 A at 60 °C, 432 A at 65 °C, and 410 A at 70 °C. If your panel ambient sits at 50 °C, you get the full 500 A; above that, the thermal curve governs the real load you can pass without nuisance tripping. The adjustable trip range (750 A minimum, 7 000 A maximum) means the ETU850 can be dialed to match the cable and load — useful when the same breaker frame covers multiple feeder sizes in a build. Interrupting capacity at 240 V hits 187 kA — that is well above typical utility fault levels in North American 120/208 V or 277/480 V panels, so you get selectivity headroom without oversizing the frame.

Integration and physical fit

The 3VA2450-5KP42-0AA0 measures 248 mm high, 184 mm wide, and 110 mm deep — a standard MCCB footprint for a 500 A frame. The 4-pole configuration handles three-phase loads plus neutral switching, common in generator paralleling or IT-system distribution. Communication function is built in, so it can report status and trip events to a higher-level control system without an add-on module.

Frequently asked questions

How do I get current pricing and availability for 3VA2450-5KP42-0AA0?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.

What is the closest functional second-source to 3VA2450-5KP42-0AA0?

The 3VA2116-5JP32-0AE0 is a smaller-frame SENTRON MCCB (160 A frame, 3-pole) with a lower interrupting capacity. It will not drop into the same panel without rewiring — the 3VA2450 is a 500 A, 4-pole frame and the 3VA2116 is a 160 A, 3-pole. For a true functional replacement at the 500 A level, stick with the 3VA2450 family.

What are the physical dimensions of 3VA2450-5KP42-0AA0?

Height is 248 mm, width is 184 mm, and depth is 110 mm. These are the standard MCCB footprint dimensions for a 500 A frame.

MPN
3VA2450-5KP42-0AA0