The 3VA2450-5KQ42-0AA0: Interrupting rating drops with system voltage: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 9 kA at 690 V. The 6 kA limited-to-1-second rating is a thermal withstand for coordination studies, not a switching rating.
Above that, derate: 477 A at 55 °C, 455 A at 60 °C, 432 A at 65 °C, 410 A at 70 °C.