Breaking capacity ranges from 187 kA at 240 V down to 17 kA at 690 V, with 121 kA at 415 V and 440 V, and 75.6 kA at 500 V — so it handles high-fault utility feeds and large motor branch circuits without upstream fusing in most installations.
Thermal performance and panel integration
Rated 500 A from 40 °C through 50 °C, then derates linearly to 480 A at 70 °C — typical for a panel with multiple breakers stacked together; plan your enclosure cooling if the ambient stays above 50 °C. The 138 mm width is a 3-pole frame; it fits standard SENTRON 3VA switchboard cutouts and DIN-rail adapters.