Skip to main content
Siemens 3VA2450-5MN32-0JA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2450-5MN32-0JA0 SENTRON MCCB, 500 A, 187 kA at 24

MPN3VA2450-5MN32-0JA0

Siemens SENTRON 3VA2450-5MN32-0JA0, molded case circuit breaker, 3-pole, 500 A, motor protection version with ETU350M electronic trip unit, shunt trip (STL), 187 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2450-5MN32-0JA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionMotor protection
Basic switch (supplied) ref.3VA2450-5MN32-0AA0
3VA2450-5MN32-0JA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C500 A
Current at 45 °C500 A
Current at 50 °C500 A
Current at 55 °C495 A
Current at 60 °C490 A
Current at 65 °C485 A
Current at 70 °C480 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V17 kA
Power loss, max.99 W
3VA2450-5MN32-0JA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M
3VA2450-5MN32-0JA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2450-5MN32-0JA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2450-5MN32-0JA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2450-5MN32-0JA0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

Per the datasheet, it carries a breaking capacity of 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V — so the SCCR headroom is substantial for most industrial distribution panels. The motor protection designation means it includes phase failure detection and a voltage trigger, making it suited for motor branch circuits where loss-of-phase protection is required.

Derating begins at 55 °C (495 A), dropping to 480 A at 70 °C. Dimensions are 248 mm height, 138 mm width, and 110 mm depth, so it fits standard MCCB mounting footprints.

The ETU350M release is the overcurrent protection brain — it's an electronic trip unit with adjustable settings (the specific curve parameters are in the full datasheet).

Frequently asked questions

What is the breaking capacity of 3VA2450-5MN32-0JA0 at 415 V?

At 415 V the breaking capacity is 121 kA. The same rating applies at 440 V; it drops to 75.6 kA at 500 V and 17 kA at 690 V.

Where can I buy 3VA2450-5MN32-0JA0 and get current pricing?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at the time of quote — submit an RFQ for a firm price and lead time.

Does 3VA2450-5MN32-0JA0 include phase failure protection?

Yes, the motor protection version includes phase failure detection as a standard function, along with a voltage trigger.

MPN
3VA2450-5MN32-0JA0