Skip to main content
Siemens 3VA2450-7MN32-0AD0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2450-7MN32-0AD0 SENTRON MCCB, 500 A, 3-Pole, Moto

MPN3VA2450-7MN32-0AD0

Siemens SENTRON 3VA2 molded case circuit breaker, 3VA2450-7MN32-0AD0, 3-pole, 500 A rated at 40 °C, motor protection design, 330 kA breaking capacity at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2450-7MN32-0AD0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2450-7MN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA2450-7MN32-0AD0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C500 A
Current at 45 °C500 A
Current at 50 °C500 A
Current at 55 °C495 A
Current at 60 °C490 A
Current at 65 °C485 A
Current at 70 °C480 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V15.3 kA
Power loss, max.99 W
3VA2450-7MN32-0AD0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2450-7MN32-0AD0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2450-7MN32-0AD0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA2450-7MN32-0AD0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2450-7MN32-0AD0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

At 55 °C it's rated 495 A, at 60 °C it's 490 A, and at 65 °C it's 485 A, dropping to 480 A at 70 °C. The interrupting capacity reaches 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 15.3 kA at 690 V.

Motor protection and auxiliary switch configuration

This MCCB includes phase failure detection and is designed for motor protection duty. It ships with the basic switch 3VA2450-7MN32-0AA0 and three HQ auxiliary switches. No undervoltage release, voltage trigger, or communication function is included. The unit does not have a trip indicator. It is rated for a short-time delay of 4 s minimum and 13 s maximum.

Dimensions are 248 mm height, 138 mm width, and 110 mm depth. Maximum power loss is 99 W. The MCCB mounts in standard panel or enclosure cutouts for SENTRON 3VA2 frame sizes.

Frequently asked questions

How do I get current pricing and availability for 3VA2450-7MN32-0AD0?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.

What is the breaking capacity of this MCCB at 240 V?

The interrupting capacity is 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 15.3 kA at 690 V.

MPN
3VA2450-7MN32-0AD0