Specifications

Identification

3VA2450-7MN32-0KC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2450-7MN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2450-7MN32-0KC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C500 A
Current at 45 °C500 A
Current at 50 °C500 A
Current at 55 °C495 A
Current at 60 °C490 A
Current at 65 °C485 A
Current at 70 °C480 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V15.3 kA
Power loss, max.99 W

Protection & Trip Unit

3VA2450-7MN32-0KC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2450-7MN32-0KC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2450-7MN32-0KC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2450-7MN32-0KC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2450-7MN32-0KC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

SENTRON 3VA2 MCCB for Motor Protection

The Siemens 3VA2450-7MN32-0KC0 is a SENTRON 3VA2-series molded case circuit breaker (MCCB) designed specifically for motor protection, carrying a continuous current rating of 500 A at 40 °C and derating to 480 A at 70 °C ambient. The 3-pole frame is built for selective coordination in motor control centers and distribution panels, with an interrupting capacity of 330 kA at 240 V AC and 242 kA at 415 V AC — the 690 V rating drops to 15.3 kA, so verify the available fault current at the point of installation. This variant ships with a shunt trip release (STL) and two auxiliary switches HQ, plus built-in phase failure detection — no separate undervoltage release is fitted. The 99 W maximum power loss at full load matters for enclosure thermal management; a panel with multiple breakers side-by-side needs ventilation or derating to stay within the 70 °C operating limit.

Integration & Mounting

The MCCB measures 248 mm high by 138 mm wide by 110 mm deep, fitting standard panel-mount cutouts for 3-pole SENTRON 3VA2 frames. The 6 kA limited-to-1-second rating is a short-time withstand figure for selective coordination downstream of a larger feeder — useful when setting the trip curve for motor starting inrush.

Frequently asked questions

Where can I buy 3VA2450-7MN32-0KC0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What are the key ratings for this MCCB?

Rated 500 A continuous at 40 °C, 3-pole, with interrupting capacity of 330 kA at 240 V, 242 kA at 415 V, and 15.3 kA at 690 V. It includes a shunt trip release, two auxiliary switches, and phase failure detection.

What is the physical size of 3VA2450-7MN32-0KC0?

The MCCB measures 248 mm high, 138 mm wide, and 110 mm deep.

MPN