Skip to main content
Siemens 3VA2450-7MS32-0KG0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2450-7MS32-0KG0 MCCB, 500 A, 3-Pole, 330

MPN3VA2450-7MS32-0KG0

Siemens SENTRON molded case circuit breaker, 3VA2450-7MS32-0KG0, 3-pole, 500 A at 40 °C, breaking capacity 330 kA at 240 V, starter protection version with ETU310M overcurrent release.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2450-7MS32-0KG0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionStarter protection
3VA2450-7MS32-0KG0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C500 A
Current at 45 °C500 A
Current at 50 °C500 A
Current at 55 °C495 A
Current at 60 °C490 A
Current at 65 °C485 A
Current at 70 °C480 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 690 V15.3 kA
Power loss, max.99 W
3VA2450-7MS32-0KG0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU310M
Overcurrent protection functionI
Ground-fault monitoringWithout
3VA2450-7MS32-0KG0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2450-7MS32-0KG0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
3VA2450-7MS32-0KG0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2450-7MS32-0KG0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.8 in
Width (in)5.4 in

Product details

That 500 A holds flat through 50 °C — only starts to derate above 55 °C, hitting 495 A at 55 °C and 480 A at 70 °C. For a panel builder, that means you can run this breaker at full nameplate in a warm enclosure without worrying about nuisance tripping, as long as ambient stays under 55 °C. Breaking capacity is the headline number here: 330 kA at 240 V, 242 kA at 415 V, and 242 kA at 440 V. The ETU310M overcurrent release gives you adjustable short-circuit pickup (li) from 1 500 A to 7 500 A, plus protection function I (instantaneous only). No ground-fault monitoring, no phase-failure detection, no communication module — this is a straightforward thermal-magnetic-style electronic trip unit for motor or feeder protection where you don't need the bells and whistles.

Footprint is 138 mm wide by 248 mm tall by 110 mm deep. That 138 mm width (5.4 inches) is a standard MCCB form factor — it'll drop into most existing panel cutouts sized for a 3-pole 500 A frame without re-drilling. Depth of 110 mm leaves room behind the door for wiring gutters or a backplate. Power loss is 99 W maximum at full load.

Frequently asked questions

What is the breaking capacity of 3VA2450-7MS32-0KG0 at 415 V?

242 kA at 415 V, and the same at 440 V. At 240 V it reaches 330 kA, and at 690 V it's 15.3 kA.

Where can I buy 3VA2450-7MS32-0KG0?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

Does this breaker include ground-fault monitoring or communication?

No. It has no ground-fault monitoring, no phase-failure detection, and no communication function. The overcurrent release is ETU310M with adjustable instantaneous pickup only.

MPN
3VA2450-7MS32-0KG0