Line protection MCCB with ETU340 trip unit
Breaking capacity is 440 kA at 240 V AC, 330 kA at 415 V and 440 V, 220 kA at 500 V, and 52.5 kA at 690 V — figures that cover most industrial service-entrance and feeder applications without needing a current-limiting upstream device. The 500 A rating holds from 40 °C through 50 °C; above that, derate linearly to 410 A at 70 °C.
If you need remote signaling or shunt-trip capability, the 3VA2 accessory platform accepts those add-ons without changing the base breaker.