Skip to main content
Siemens 3VA2463-5HK42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2463-5HK42-0AA0 SENTRON MCCB, 630 A, 4-Pole, ETU3

MPN3VA2463-5HK42-0AA0
Active

Siemens SENTRON 3VA2463-5HK42-0AA0, molded case circuit breaker, 4-pole, 630 A, ETU340 electronic trip unit, line protection version.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2463-5HK42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2463-5HK42-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C630 A
Current at 45 °C612 A
Current at 50 °C593 A
Current at 55 °C575 A
Current at 60 °C557 A
Current at 65 °C538 A
Current at 70 °C520 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V9 kA
Power loss, max.162 W
3VA2463-5HK42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU340
Overcurrent protection functionELISA LI
Ground-fault monitoringWithout
3VA2463-5HK42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2463-5HK42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2463-5HK42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2463-5HK42-0AA0 — Mechanical
ParameterValue
Height248 mm
Width184 mm
Depth110 mm
Height (in)9.76 in
Width (in)7.24 in
Depth (in)4.33 in

Product details

The frame is sized for panel mounting — 248 mm high, 184 mm wide, 110 mm deep — so it occupies a standard MCCB footprint in a distribution board or motor control center.

This breaker's interrupting rating changes with system voltage, which is the key selection parameter for fault-current coordination. At 240 V it clears 187 kA; at 415 V or 440 V that drops to 121 kA; at 500 V it's 75.6 kA; and at 690 V it's 9 kA. The 9 kA at 690 V still handles most 690 V motor branch circuits.

Thermal derating — real-world current

Above that, the breaker must be derated: 612 A at 45 °C, 593 A at 50 °C, 575 A at 55 °C, 557 A at 60 °C, 538 A at 65 °C, and 520 A at 70 °C.

Trip unit and adjustments

The ETU340 electronic trip unit provides adjustable neutral conductor protection: OFF, 50%, or 100% of the phase rating. Front-side protection is IP40.

Frequently asked questions

How do I get current pricing and availability for 3VA2463-5HK42-0AA0?

Submit an RFQ through this listing. The part is sourced to order; pricing and stock are confirmed at quote time.

What is 3VA2463-5HK42-0AA0's depth?

The depth is 110 mm (4.33 in). Overall dimensions are 248 mm high by 184 mm wide.

What breaking capacity does this MCCB have at 415 V?

At 415 V the interrupting rating is 121 kA. At 240 V it is 187 kA, at 500 V it is 75.6 kA, and at 690 V it is 9 kA.

What trip unit does 3VA2463-5HK42-0AA0 use?

It uses the ETU340 electronic overcurrent release. Neutral protection is adjustable: OFF, 50%, or 100%.

MPN
3VA2463-5HK42-0AA0