Siemens 3VA2463-5HL32-0AL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2463-5HL32-0AL0 SENTRON MCCB, 630 A, 3-Pole, ETU3

MPN3VA2463-5HL32-0AL0

Siemens SENTRON 3VA2463-5HL32-0AL0, molded case circuit breaker, 3-pole, 630 A, ETU320 electronic release, line protection version.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2463-5HL32-0AL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2463-5HL32-0AL0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C630 A
Current at 45 °C612 A
Current at 50 °C593 A
Current at 55 °C575 A
Current at 60 °C557 A
Current at 65 °C538 A
Current at 70 °C520 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V55 kA
Breaking capacity at 500 V36 kA
Breaking capacity at 690 V9 kA
Power loss, max.162 W
3VA2463-5HL32-0AL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2463-5HL32-0AL0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2463-5HL32-0AL0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
3VA2463-5HL32-0AL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2463-5HL32-0AL0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.8 in
Width (in)5.4 in

Product details

The Siemens SENTRON 3VA2463-5HL32-0AL0 is a 3-pole molded case circuit breaker rated for a continuous current of 630 A at 40 °C, with the ETU320 electronic trip unit providing adjustable long-time delay (tr) from 0.5 s to 12 s and an adjustable Ir up to 630 A. The thermal derating curve is published: 630 A at 40 °C, 612 A at 45 °C, 593 A at 50 °C, 575 A at 55 °C, 557 A at 60 °C, 538 A at 65 °C, and 520 A at 70 °C.

The 138 mm width (5.4 in) is the standard 3-pole MCCB footprint for this class — it occupies three 45 mm pole spaces on a DIN rail or panel-mount base. The 110 mm depth includes the rear arc chamber and front rotary handle; verify clearance behind the panel for the arc exhaust and cable bending radius.

Environmental and endurance specs

Frequently asked questions

Where can I buy 3VA2463-5HL32-0AL0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the interrupting capacity of 3VA2463-5HL32-0AL0 at 415 V?

121 kA at 415 V, which covers most industrial service-entrance and large-feeder fault levels.

What is the thermal derating at 50 °C for this breaker?

593 A at 50 °C, down from 630 A at 40 °C. Derate per the published curve for ambient above 40 °C.

What trip unit does 3VA2463-5HL32-0AL0 use?

The ETU320 electronic release with adjustable long-time delay (tr 0.5 s to 12 s) and adjustable Ir up to 630 A.