Siemens 3VA2463-5HL32-0AL0
MPN3VA2463-5HL32-0AL0
circuit breaker 3VA2 IEC frame 630 breaking capacity class M Icu=55kA @ 415V 3-pole, line protection ETU320, LI, In=630A overload protection Ir=250A...630A short-circuit protection Ii=1.5...9x In nut keeper kit 2 auxiliary switches 1 trip alarm switch 1 electrical alarm switch
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jun 2026
Specifications
Identification
| Parameter | Value |
|---|---|
| Product designation | Molded case circuit breaker |
| Brand / range | SENTRON |
| Product version | Line protection |
Ratings
| Parameter | Value |
|---|---|
| Number of poles | 3 |
| Current at 40 °C | 630 A |
| Current at 45 °C | 612 A |
| Current at 50 °C | 593 A |
| Current at 55 °C | 575 A |
| Current at 60 °C | 557 A |
| Current at 65 °C | 538 A |
| Current at 70 °C | 520 A |
| Switching capacity class | M |
| Breaking capacity at 240 V | 187 kA |
| Breaking capacity at 415 V | 121 kA |
| Breaking capacity at 440 V | 55 kA |
| Breaking capacity at 500 V | 36 kA |
| Breaking capacity at 690 V | 9 kA |
| Power loss, max. | 162 W |
Protection & Trip Unit
| Parameter | Value |
|---|---|
| Overcurrent release (trip unit) type | ETU320 |
Construction & Connection
| Parameter | Value |
|---|---|
| Main circuit connection type | Lug terminal |
| Main circuit connector arrangement | Front terminal |
| Protection class (IP), front | IP40 |
Accessories & Functions
| Parameter | Value |
|---|---|
| Communication function | No |
| Measurement function | No |
| Motor drive option | Yes |
Environmental
| Parameter | Value |
|---|---|
| Operating temperature, max. | 70 °C |
| Operating temperature, min. | -25 °C |
| Storage temperature, max. | 80 °C |
| Storage temperature, min. | -40 °C |
Mechanical
| Parameter | Value |
|---|---|
| Height | 248 mm |
| Width | 138 mm |
| Depth | 110 mm |
| Height (in) | 9.8 in |
| Width (in) | 5.4 in |
MPN
3VA2463-5HL32-0AL0