Skip to main content
Siemens 3VA2463-5HL32-0CC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2463-5HL32-0CC0 SENTRON MCCB, 630 A, 187 kA at 24

MPN3VA2463-5HL32-0CC0

Siemens SENTRON 3VA2463-5HL32-0CC0, 3-pole molded case circuit breaker, 630 A rated continuous current Iu, ETU320 electronic trip unit, 187 kA at 240 V, 110 x 138 x 248 mm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2463-5HL32-0CC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2463-5HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA2463-5HL32-0CC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C630 A
Current at 45 °C612 A
Current at 50 °C593 A
Current at 55 °C575 A
Current at 60 °C557 A
Current at 65 °C538 A
Current at 70 °C520 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V17 kA
Power loss, max.164.5 W
3VA2463-5HL32-0CC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2463-5HL32-0CC0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2463-5HL32-0CC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2463-5HL32-0CC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2463-5HL32-0CC0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

The Siemens SENTRON 3VA2463-5HL32-0CC0 is a 3-pole molded case circuit breaker (MCCB) rated for 630 A continuous current (Iu) at 40 °C, with an ETU320 electronic trip unit. That 630 A figure is the base rating — the breaker can carry that load continuously in a 40 °C ambient without tripping. Above 40 °C, the current must be derated: at 50 °C it handles 593 A, at 60 °C it handles 557 A, and at 70 °C it handles 520 A. For a panel running hot near the top of a sealed enclosure, that derating curve is what decides whether this frame size works or you need to step up. Breaking capacity is the other headline: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V.

Trip unit, auxiliaries, and release options

The ETU320 is an electronic overcurrent release — it provides LI (long-time and short-time) protection with adjustable pickups and time delays, plus instantaneous (I) protection. Latching endurance is rated at 15 000 cycles, which is typical for a fixed-mounted MCCB in a distribution board where it is not switched daily.

Dimensions: 248 mm height, 138 mm width, 110 mm depth. No communication function or phase-failure detection on this variant — it is a straight line-protection breaker.

Frequently asked questions

How do I get current pricing and availability for 3VA2463-5HL32-0CC0?

Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through independent distribution channels.

What are the key ratings for 3VA2463-5HL32-0CC0?

Rated continuous current Iu is 630 A at 40 °C, rated insulation voltage Ui is 800 V, breaking capacity is 187 kA at 240 V and 121 kA at 415 V. It is a 3-pole MCCB with an ETU320 electronic trip unit.

What compliance documentation is available for 3VA2463-5HL32-0CC0?

As a Siemens SENTRON series MCCB, it carries CE marking and is designed to IEC 60947-2. UL and CSA listings are standard for the 3VA family; specific certification marks for this exact order code should be confirmed from the manufacturer's declaration of conformity.

MPN
3VA2463-5HL32-0CC0