Siemens 3VA2463-5HL32-0CL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2463-5HL32-0CL0 SENTRON MCCB, 630 A, 3-Pole, ETU3

MPN3VA2463-5HL32-0CL0

Siemens SENTRON 3VA2, Molded case circuit breaker, 3VA2463-5HL32-0CL0, 3-pole, 630 A, ETU320, line protection, 187 kA at 240 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2463-5HL32-0CL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2463-5HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22
3VA2463-5HL32-0CL0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C630 A
Current at 45 °C612 A
Current at 50 °C593 A
Current at 55 °C575 A
Current at 60 °C557 A
Current at 65 °C538 A
Current at 70 °C520 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V17 kA
Power loss, max.164.5 W
3VA2463-5HL32-0CL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2463-5HL32-0CL0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2463-5HL32-0CL0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4
3VA2463-5HL32-0CL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2463-5HL32-0CL0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

Siemens 3VA2463-5HL32-0CL0 — 630 A SENTRON MCCB with ETU320 Release

The Siemens 3VA2463-5HL32-0CL0 is a SENTRON 3VA2 molded case circuit breaker (MCCB) rated for 630 A continuous current at 40 °C, in a 3-pole configuration with an ETU320 electronic trip unit. This is the line-protection version — no voltage trigger, no communication module, no phase-failure detection built in. The interrupting ratings climb to 187 kA at 240 V and hold at 121 kA through 415–440 V, then taper to 75.6 kA at 500 V and 17 kA at 690 V.

If your panel runs hotter — and most enclosed switchboards do — derate per the table: 612 A at 45 °C, 593 A at 50 °C, 575 A at 55 °C, 557 A at 60 °C, 538 A at 65 °C, and 520 A at 70 °C. That derating curve is what you use for the NEC 110.14(B) temperature correction in a UL 489 listing context. The ETU320 is a basic electronic trip with LS (long-time and short-time) protection; it's not the full LSIG you'd get on the ETU600, but for feeder protection without ground-fault it's the standard choice.

Integration Notes

The undervoltage release (UVR) is installed; verify coil voltage matches your control circuit before energizing. Maximum power dissipation is 164.5 W at rated current — account for that heat in your enclosure sizing, especially if the breaker is enclosed in a low-volume pull box rather than a ventilated switchboard.

Frequently asked questions

Where can I buy 3VA2463-5HL32-0CL0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the interrupting rating of 3VA2463-5HL32-0CL0 at 415 V?

The interrupting rating is 121 kA at 415 V. It also carries 187 kA at 240 V, 121 kA at 440 V, 75.6 kA at 500 V, and 17 kA at 690 V.

What trip unit does 3VA2463-5HL32-0CL0 use?

It uses the ETU320 electronic trip unit, which provides LS (long-time and short-time) protection. It does not include ground-fault protection or communication functions.

MPN